Worked example
Example: Workshop 20 x 10 x 4 m, 4 000 m³/h, target 6. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Room length | 20.000 m |
| Room width | 10.000 m |
| Room height | 4.0000 m |
| Supply (or extract) airflow | 4,000.0 m³/h |
| Target air changes per hour | 6.0000 1/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Room volume | 800.00 m³ |
| Air changes per hour | 5.0000 1/h |
| Airflow for the target air changes | 4,800.0 m³/h |
Open this example in the calculator and change any input.
Formula
\(V = L W H\)
\(n = Q / V\)
\(Q_t = n_t V\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | length | m |
| \(W\) | width | m |
| \(H\) | height | m |
| \(Q\) | airflow | m³/s |
| \(n_t\) | target air changes | 1/s |
| \(V\) | room volume | m³ |
| \(n\) | air changes | 1/s |
| \(Q_t\) | airflow for the target | m³/s |
Method and standards
An air change is a volume of air equal to the room volume; the rate is airflow over volume.
Where it is used
- Sizing exhaust fans for battery rooms and boiler houses.
- Checking ventilation in workshops and stores.
- Converting ventilation rules into fan duty.
Common mistakes
- Using floor area instead of volume.
- Assuming perfect mixing in tall spaces.
- Ignoring makeup air.
Assumptions and limits
- Perfect mixing; constant room volume.
References
- ACH = Q / V
Questions and answers
How many air changes does 4 000 m³/h give in a 20 × 10 × 4 m room?
5 per hour; 6 per hour needs 4 800 m³/h.
What air change rate do rooms need?
It depends on use and local codes: battery rooms, boiler houses, kitchens and offices all differ; use the rate your code or standard requires.
Is ACH enough to design ventilation?
Often not: heat removal, fumes or occupancy may need more; check each.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.