Sensible Heat Ratio, Apparatus Dew Point and Supply Air

Room sensible heat ratio, the coil's apparatus dew point on the room ratio line, supply air temperature from the bypass factor, and the supply air flow.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 24 °C, 50 %, 30 + 8 kW, BF 0.1Humid room 26 °C, 55 %, SHR 0.65

Results

Room ratio line from Q_s = ṁc_pm(t_r − t_s) and Q_l = ṁh_fg(W_r − W_s) with c_pm = 1.006 + 1.86W_r kJ/(kg·K), h_fg = 2,501 kJ/kg. Supply air flow is at the supply state.

Room sensible heat ratio0.78947
Apparatus dew point10.341°C
Supply air temperature11.707°C
Supply humidity ratio7.9587g/kg
Supply air flow7,017.0m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 24 °C, 50 %, 30 + 8 kW, BF 0.1. The inputs, in the units selected above:

InputValue
Room temperature24.000 °C
Room relative humidity50.000 %
Room sensible load30.000 kW
Room latent load8.0000 kW
Coil bypass factor10.000 %
Barometric pressure101.33 kPa

Applying the formula below gives:

ResultValue
Room sensible heat ratio0.78947
Apparatus dew point10.341 °C
Supply air temperature11.707 °C
Supply humidity ratio7.9587 g/kg
Supply air flow7,017.0 m³/h

Open this example in the calculator and change any input.

Formula

\(SHR = \frac{Q_s}{Q_s + Q_l}, \quad W_{sat}(t_{adp}) = W_r - \frac{Q_l}{Q_s}\frac{c_{pm}}{h_{fg}}(t_r - t_{adp}), \quad t_s = t_{adp} + BF(t_r - t_{adp})\)

\(c_{pm} = c_{p,a} + c_{p,v}W_r, \quad W_s = W_r - \frac{Q_l}{Q_s}\frac{c_{pm}}{h_{fg}}(t_r - t_s), \quad \dot V_s = \frac{Q_s}{c_{pm}(t_r - t_s)}\,v_s\)

Variables

Symbol Meaning SI unit
\(t_r\) Room temperature K
\(\varphi_r\) Room relative humidity -
\(Q_s\) Room sensible load W
\(Q_l\) Room latent load W
\(BF\) Coil bypass factor -
\(p\) Barometric pressure Pa
\(SHR\) Room sensible heat ratio -
\(t_{adp}\) Apparatus dew point K
\(t_s\) Supply air temperature K
\(W_s\) Supply humidity ratio kg/kg
\(\dot V_s\) Supply air flow m³/s
\(W_r\) Room humidity ratio kg/kg
\(W_{sat}\) Saturation humidity ratio kg/kg
\(c_{pm}\) Moist-air specific heat per kg dry air J/(kg·K)
\(c_{p,a}\) Dry-air specific heat, 1 006 J/(kg·K)
\(c_{p,v}\) Water-vapour specific heat, 1 860 J/(kg·K)
\(h_{fg}\) Latent heat used, 2 501 000 J/kg
\(v_s\) Specific volume of the supply air per kg dry air m³/kg

Method and standards

Room ratio line.

Where it is used

  • Cooling coil selection.
  • Checking whether a coil can hold room humidity.

Common mistakes

  • Using grand SHR (with fresh air) for the room line.
  • Ignoring bypass factor.

Assumptions and limits

  • Room load only; no fan or duct gains.
  • The latent load is converted with h_fg = 2 501 kJ/kg (the 0 °C value of the ASHRAE moist-air enthalpy) and c_pm = 1.006 + 1.86 W_r kJ/(kg·K). The supply air flow from room load calculator uses the vapour enthalpy at room temperature (about 2 545 kJ/kg), so the two give supply humidity ratios about 1.7 % apart for the same loads.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 1 (moist-air processes); Carrier
  • Handbook of Air Conditioning System Design (ADP and bypass factor method)

Questions and answers

What is the apparatus dew point?

The effective coil surface temperature: where the room ratio line meets the saturation curve.

Why does a low SHR need a cold coil?

More moisture must be removed per unit of cooling, so the ratio line is steeper and meets saturation at a lower temperature.

What do the defaults represent?

An office-type room at 24 °C and 50 % with a moderate latent share and a typical bypass factor.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.