Worked example
Example: Summer 10 000 m³/h, 40 °C outside, 24 °C exhaust, 70 %, 3 000 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fresh (outdoor) air flow | 10,000 m³/h |
| Atmospheric pressure | 101.33 kPa |
| Outdoor air temperature | 40.000 °C |
| Outdoor air humidity ratio | 12.000 g/kg |
| Exhaust (room) air temperature | 24.000 °C |
| Sensible effectiveness (equal air flows) | 70.000 % |
| Running hours per year at this condition | 3,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fresh air temperature after the recovery unit | 28.800 °C |
| Dry air flow | 11,059 kg/h |
| Sensible heat recovered (heating or cooling) | 35.380 kW |
| Energy recovered per year | 106,141 kWh |
Open this example in the calculator and change any input.
Formula
\(T_s = T_o + \varepsilon (T_r - T_o)\)
\(Q_r = \dot m_a |h(T_s, W_o) - h(T_o, W_o)|\)
\(E = Q_r t_y\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | fresh air flow | m³/s |
| \(p\) | atmospheric pressure | Pa |
| \(T_o\) | outdoor temperature | K |
| \(W_o\) | outdoor humidity ratio | kg/kg |
| \(T_r\) | exhaust temperature | K |
| \(\varepsilon\) | sensible effectiveness | - |
| \(t_y\) | hours per year | s |
| \(h\) | moist air enthalpy (ASHRAE) | J/kg |
| \(T_s\) | fresh air temperature after recovery | K |
| \(\dot m_a\) | dry air flow | kg/s |
| \(Q_r\) | heat recovered | W |
| \(E\) | energy per year | J |
Method and standards
Sensible effectiveness is the fraction of the possible temperature change achieved; with equal flows the supply leaves at T_o + ε (T_r − T_o). The heat recovered is the dry air flow times the enthalpy change at constant humidity.
Where it is used
- Evaluating heat recovery on fresh-air units.
- Estimating payback of a wheel or plate exchanger.
- Comparing recovery devices.
Common mistakes
- Counting recovery when outdoor air is already near room temperature.
- Ignoring the added fan power.
- Using total effectiveness for a sensible-only device.
Assumptions and limits
- Equal supply and exhaust flows; sensible only. An outdoor humidity ratio above saturation is flagged.
References
- Sensible effectiveness definition
- ASHRAE psychrometrics
Questions and answers
What does a 70 % wheel recover on 10 000 m³/h of 40 °C fresh air with 24 °C exhaust?
It cools the fresh air to about 28.8 °C, saving about 35 kW of sensible cooling.
Does it work in winter too?
Yes: the same wheel preheats cold fresh air from the warm exhaust.
What about humidity?
This is sensible recovery only; an enthalpy wheel also transfers moisture and saves more in humid climates.