FireCADCalc

Heating or Cooling Energy from Degree-Days

Seasonal heating or cooling energy of a building from its heat loss coefficient (UA) and degree-days, with the fuel or electricity needed.

Inputs

Examples: Heating with oilCooling with a chiller (COP 3.5)

For your site and base temperature, from weather data.

Results

Degree-days must use a base temperature that suits the building's balance point.

Heat or cooling delivered132,000kWh
Energy input155,294kWh
Fuel (if NCV given)13,311kg
Cost998,319

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Heating with oil. The inputs, in the units selected above:

InputValue
Heat loss coefficient (fabric and ventilation)2.5000 kW/K
Degree-days (K·day)2,200.0 -
System efficiency (heating, NCV basis) or COP (cooling)0.85000 -
Fuel net calorific value (0 for electricity)42.000 MJ/kg
Price per kg of fuel or per kWh75.000 -

Applying the formula below gives:

ResultValue
Heat or cooling delivered132,000 kWh
Energy input155,294 kWh
Fuel (if NCV given)13,311 kg
Cost998,319

Open this example in the calculator and change any input.

Formula

\(Q = UA \cdot DD \cdot 86\,400, \quad E = \frac{Q}{\eta}, \quad m_f = \frac{E}{NCV}, \quad C = m_f\,c\ \ \text{(fuel)}\ \text{or}\ C = \frac{E}{3.6\times10^6}\,c\ \ \text{(electricity, per kWh)}\)

Variables

Symbol Meaning SI unit
\(UA\) Heat loss coefficient (fabric and ventilation) W/K
\(DD\) Degree-days (K·day) -
\(\eta\) System efficiency (heating, NCV basis) or COP (cooling) -
\(NCV\) Fuel net calorific value (0 for electricity) J/kg
\(c\) Price per kg of fuel or per kWh -
\(Q\) Heat or cooling delivered J
\(E\) Energy input J
\(m_f\) Fuel (if NCV given) kg
\(C\) Cost -

Method and standards

Degree-day method.

Where it is used

  • Fuel budgets for heating colonies and offices.
  • Comparing insulation options.

Common mistakes

  • Wrong base temperature.
  • Mixing heating and cooling days.

Assumptions and limits

  • Steady UA.
  • The fuel quantity uses the net calorific value, so the heating efficiency must be on the NCV basis too; a GCV-based efficiency mis-states the fuel by the GCV/NCV ratio (about 5–11 %).

References

  • Degree-day method Q = UA × DD × 24 h (CIBSE TM41; ASHRAE Handbook—Fundamentals ch. 19)

Questions and answers

UA 2500 W/K and 2200 K·day?

132,000 kWh of heat; at 85 % that is about 13,311 kg of fuel oil.

Cooling?

Use cooling degree-days and the chiller COP as the efficiency, with NCV 0 for electricity.

Why does the base temperature matter?

Internal and solar gains supply the first few degrees.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.