Worked example
Example: Near a hot casing. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air temperature | 26.000 °C |
| Mean radiant temperature | 36.000 °C |
| Convective coefficient | 3.1000 W/(m²·K) |
| Radiative coefficient | 4.7000 W/(m²·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Operative temperature | 32.026 °C |
| Simple average (low air speed) | 31.000 °C |
Open this example in the calculator and change any input.
Formula
\(T_o = \frac{h_c T_a + h_r \bar T_r}{h_c + h_r}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_a\) | Air temperature | K |
| \(\bar T_r\) | Mean radiant temperature | K |
| \(h_c\) | Convective coefficient | W/(m²·K) |
| \(h_r\) | Radiative coefficient | W/(m²·K) |
| \(T_o\) | Operative temperature | K |
| \(T_{avg}\) | Simple average (low air speed) | K |
Method and standards
Weighted mean.
Where it is used
- Boiler house and turbine floor working conditions.
- Comfort checks near glazing.
Common mistakes
- Ignoring radiant heat near hot plant.
- Using globe temperature as mean radiant.
Assumptions and limits
- Steady exposure.
References
- Operative temperature as the h-weighted mean of air and mean radiant temperatures (ASHRAE Handbook—Fundamentals ch. 9)
Questions and answers
26 °C air with 36 °C mean radiant temperature?
About 32 °C operative.
Why weight by h?
Each part's share of a person's heat exchange sets its weight.
Higher air speed?
h_c rises, so air temperature counts more.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.