FireCADCalc

Heat Gain from Electric Motors in a Room

Heat released into a room by an electric motor and its driven machine, for motor and machine both inside, motor outside, or machine outside the room.

Inputs

Examples: Two pumps, both in the roomMotor outside, machine inMotor in, machine outside

Results

Heat per motor13.187kW
Total heat to the room26.374kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Two pumps, both in the room. The inputs, in the units selected above:

InputValue
Motor rated output15.000 kW
Load factor (share of rated output)80.000 %
Use factor (share of time running)100.00 %
Motor efficiency at that load91.000 %
ArrangementMotor and driven machine in the room
Number of such motors2.0000 -

Applying the formula below gives:

ResultValue
Heat per motor13.187 kW
Total heat to the room26.374 kW

Open this example in the calculator and change any input.

Formula

\(\dot Q = \frac{P_r F_{LM} F_{UM}}{\eta_m}, \quad P_r F_{LM} F_{UM}, \quad P_r F_{LM} F_{UM}\frac{1 - \eta_m}{\eta_m}\)

Variables

Symbol Meaning SI unit
\(P_r\) Motor rated output W
\(F_{LM}\) Load factor (share of rated output) -
\(F_{UM}\) Use factor (share of time running) -
\(\eta_m\) Motor efficiency at that load -
\(\text{arrangement}\) Arrangement -
\(n\) Number of such motors -
\(\dot Q_1\) Heat per motor W
\(\dot Q\) Total heat to the room W

Method and standards

Energy balance.

Where it is used

  • Pump houses, compressor rooms and MCC rooms.
  • Ventilation sizing.

Common mistakes

  • Nameplate without load factor.
  • Wrong arrangement.

Assumptions and limits

  • Steady running.

References

  • Motor heat gain for the three arrangements
  • P/η
  • P and P(1 − η)/η (ASHRAE Handbook—Fundamentals ch. 18)

Questions and answers

Two 15 kW pumps at 80 % load, 91 % efficient, both in the room?

About 26 kW of heat.

Motor inside, pump outside?

Only the losses: about 2.4 kW.

Why does a pump's work end as heat?

Unless it leaves with the fluid, the machine's work is dissipated in the room.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.