Worked example
Example: Room 24 °C 50 %, 35 + 8 kW, supply 13 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Room sensible load | 35.000 kW |
| Room latent load | 8.0000 kW |
| Room dry bulb | 24.000 °C |
| Room relative humidity | 50.000 % |
| Supply dry bulb | 13.000 °C |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dry-air mass flow | 11,214 kg/h |
| Supply air volume (at the supply state) | 9,211.8 m³/h |
| Supply humidity ratio | 8.2911 g/kg |
| Supply relative humidity | 88.982 % |
| Room sensible heat ratio | 81.395 % |
Open this example in the calculator and change any input.
Formula
\(\dot Q_s = \dot m_{da}(c_{pa} + W_s c_{pv})(T_r - T_s), \quad \dot Q_l = \dot m_{da}(W_r - W_s)\, h_g(T_r)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q_s\) | Room sensible load | W |
| \(\dot Q_l\) | Room latent load | W |
| \(T_r\) | Room dry bulb | K |
| \(\varphi_r\) | Room relative humidity | - |
| \(T_s\) | Supply dry bulb | K |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(\dot m_{da}\) | Dry-air mass flow | kg/s |
| \(\dot V_s\) | Supply air volume (at the supply state) | m³/s |
| \(W_s\) | Supply humidity ratio | kg/kg |
| \(\varphi_s\) | Supply relative humidity | - |
| \(SHR\) | Room sensible heat ratio | - |
Method and standards
Energy and moisture balance on the room.
Where it is used
- AHU and fan coil selection.
- Control room and MCC room air conditioning.
Common mistakes
- Volume at room instead of supply state.
- Ignoring latent load.
Assumptions and limits
- Steady state, perfect mixing.
- The latent load is converted to moisture with the vapour enthalpy at room temperature, h_g = 2501 + 1.86 t kJ/kg (t in °C). Calculators that use 2501 kJ/kg alone (for example the sensible heat ratio and ADP calculator) give a supply humidity about 1–2 % different; both are common textbook forms.
References
- Moist-air energy and moisture balances (ASHRAE Handbook—Fundamentals ch. 1 properties)
Questions and answers
35 kW sensible and 8 kW latent, room 24 °C 50 %, supply 13 °C?
About 3.1 kg/s of dry air, roughly 9,200 m³/h at the supply state.
Why does latent load change the supply humidity?
The supply air must be drier than the room by enough to absorb the moisture.
Supply RH above 100 %?
The chosen supply temperature cannot carry the latent load; lower it or add reheat.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.