Ventilation Rate from CO₂ Concentration (Mass Balance)

Outdoor air needed to hold a room's CO₂ at a limit from the number of people and their CO₂ generation, or the steady CO₂ for a given flow.

Inputs

Examples: 25 people, 1000 ppmControl room, 800 ppm

Depends on activity; your handbook's figure (about 0.005 L/s for office work).

Results

Steady-state mass balance with perfect mixing; CO₂ shows occupancy, not every pollutant.

Outdoor air needed224.14L/s
Per person8.9655L/s
Steady CO₂ with the actual flow (ppm)1,070.0

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 people, 1000 ppm. The inputs, in the units selected above:

InputValue
Number of people25.000 -
CO₂ generation per person0.005200 L/s
Indoor CO₂ limit (ppm)1,000.0 -
Outdoor CO₂ (ppm)420.00 -
Actual outdoor air flow (for the steady level)200.00 L/s

Applying the formula below gives:

ResultValue
Outdoor air needed224.14 L/s
Per person8.9655 L/s
Steady CO₂ with the actual flow (ppm)1,070.0

Open this example in the calculator and change any input.

Formula

\(\dot V = \frac{n G}{(C_i - C_o)\times10^{-6}}\)

Variables

Symbol Meaning SI unit
\(n\) Number of people -
\(G\) CO₂ generation per person m³/s
\(C_i\) Indoor CO₂ limit (ppm) -
\(C_o\) Outdoor CO₂ (ppm) -
\(\dot V_a\) Actual outdoor air flow (for the steady level) m³/s
\(\dot V\) Outdoor air needed m³/s
\(\dot V/n\) Per person m³/s
\(C_{ss}\) Steady CO₂ with the actual flow (ppm) -

Method and standards

Mass balance.

Where it is used

  • Control rooms, offices and meeting rooms.
  • Demand-controlled ventilation set points.

Common mistakes

  • ppm used as a fraction.
  • Ignoring outdoor CO₂.

Assumptions and limits

  • Perfect mixing, steady state.
  • The steady CO₂ is shown only for an actual flow above zero.

References

  • Steady-state mass balance V = n G/(C_i − C_o)

Questions and answers

25 people, 1000 ppm limit, 420 outdoors?

About 224 L/s, 9.0 L/s per person.

Why use CO₂?

It tracks occupancy and is easy to measure.

Short meetings?

CO₂ takes time to build up; the steady value is the upper bound.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.