Worked example
Example: Turbine hall, 15 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Free area of the low openings | 4.0000 m² |
| Free area of the high openings | 4.0000 m² |
| Height between opening centres | 15.000 m |
| Indoor temperature | 40.000 °C |
| Outdoor temperature | 30.000 °C |
| Discharge coefficient | 0.61000 - |
| Air density for the heat removed | 1.2000 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Effective area (openings in series) | 2.8284 m² |
| Stack flow | 19,038 m³/h |
| Heat removed ρ c_p V ΔT (c_p 1006 J/(kg·K)) | 63.841 kW |
Open this example in the calculator and change any input.
Formula
\(\dot V = C_d A_e\sqrt{\frac{2 g H |T_i - T_o|}{T_w}}, \quad T_w = \max(T_i, T_o), \quad \frac{1}{A_e^2} = \frac{1}{A_1^2} + \frac{1}{A_2^2}, \quad \dot Q = \rho c_p \dot V |T_i - T_o|\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(A_1\) | Free area of the low openings | m² |
| \(A_2\) | Free area of the high openings | m² |
| \(H\) | Height between opening centres | m |
| \(T_i\) | Indoor temperature | K |
| \(T_o\) | Outdoor temperature | K |
| \(C_d\) | Discharge coefficient | - |
| \(A_e\) | Effective area (openings in series) | m² |
| \(\dot V\) | Stack flow | m³/s |
| \(\dot Q\) | Heat removed ρ c_p V ΔT (c_p 1006 J/(kg·K)) | W |
| \(\rho\) | Air density for the heat removed | kg/m³ |
| \(c_p\) | Specific heat of air, 1 006 | J/(kg·K) |
| \(T_w\) | The warmer of T_i and T_o (absolute) | K |
| \(g\) | Standard gravity, 9.806 65 | m/s² |
Method and standards
Bernoulli with buoyancy.
Where it is used
- Turbine halls, boiler houses and warehouses.
- Smoke and heat vents.
Common mistakes
- Gross instead of free area.
- Ignoring wind.
Assumptions and limits
- Still air, well-mixed interior.
- The buoyancy term divides by the warmer absolute temperature, so the same formula holds when the inside is colder than outside (flow reversed).
- The air density for the heat removed is an input (default 1.2 kg/m³); use the density at the outlet air temperature, about 1.13 kg/m³ at 40 °C.
References
- Buoyancy-driven flow Q = C_d A_e √(2gHΔT/T)
- openings in series 1/A_e² = 1/A₁² + 1/A₂² (CIBSE AM10; ASHRAE Handbook—Fundamentals ch. 16)
Questions and answers
4 m² low and high, 15 m apart, 40 °C inside, 30 °C out?
About 5.3 m³/s (19,000 m³/h), removing some 64 kW.
Why combine the areas?
Air must pass both; the smaller one controls.
Turbine halls?
Tall halls with roof monitors rely on this.