Worked example
Example: 60 m stack, gas 150 °C, ambient 30 °C, sea level. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Stack height above the gas inlet | 60.000 m |
| Ambient air temperature | 30.000 °C |
| Mean flue gas temperature in the stack | 150.00 °C |
| Flue gas molar mass | 30.000 kg/kmol |
| Site pressure from | Altitude (ISO 2533 standard atmosphere) |
| Site altitude above sea level | 0 m |
| Barometric pressure at the site (absolute) | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Theoretical natural draught | 18.026 mmWC |
| Ambient air density | 1.1644 kg/m³ |
| Flue gas density in the stack | 0.86399 kg/m³ |
| Barometric pressure used | 1.0132 bar |
Open this example in the calculator and change any input.
Formula
\(\Delta p = g\,H\,(\rho_a - \rho_g) \qquad \rho = \frac{p\,M}{R\,T}\)
Site pressure from the ISO 2533 standard atmosphere (troposphere):
\(p = p_0\left(1 - \frac{L\,z}{T_0}\right)^{\frac{g\,M_{ISA}}{R^*\,L}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(H\) | stack height above the gas inlet | m |
| \(T_a\) | ambient air temperature | K |
| \(T_g\) | mean flue gas temperature in the stack | K |
| \(M_g\) | flue gas molar mass | kg/kmol |
| \(\text{site}\) | site pressure from altitude or entered | – |
| \(z\) | site altitude above sea level | m |
| \(p_s\) | barometric pressure entered | Pa |
| \(\Delta p\) | theoretical natural draught | Pa |
| \(\rho_a\) | ambient air density | kg/m³ |
| \(\rho_g\) | flue gas density in the stack | kg/m³ |
| \(p\) | barometric pressure used | Pa |
| \(g\) | standard gravity, 9.806 65 | m/s² |
| \(R\) | universal gas constant, 8.314 462 618 | J/(mol·K) |
| \(M\) | molar mass (dry air 28.96 kg/kmol, or \(M_g\)) | kg/kmol |
| \(p_0\), \(T_0\), \(L\) | ISO 2533 sea-level pressure 101 325 Pa, temperature 288.15 K, lapse rate 0.0065 K/m | – |
| \(M_{ISA}\), \(R^*\) | ISO 2533 air molar mass 28.964 42 kg/kmol and gas constant 8.314 32 J/(mol·K) | – |
Method and standards
Hydrostatic pressure difference between a column of ambient air and a column of flue gas of the same height, both ideal gases at the site pressure. The site pressure is either entered or taken from the ISO 2533:1975 standard atmosphere at the altitude; ISO 2533's own constants are used in the barometric formula so that its tabulated pressures are reproduced. Dry air molar mass from the ASME PTC 4 composition and IUPAC atomic weights.
Where it is used
- Natural-draught boilers and furnaces.
- Checking draught available against the system loss.
- Stack height studies.
Common mistakes
- Using sea-level air density at a hill site.
- Ignoring gas cooling up the stack.
- Forgetting friction losses in the stack.
Assumptions and limits
- Theoretical (static) draught; friction, exit velocity head and fittings losses are not deducted.
- Mean gas temperature over the height; cooling along a tall unlined steel stack lowers it.
- Dry ambient air; humidity lowers the air density, by about 1–1.5 % in hot humid air (30 °C, 80 % RH), which reduces the draught by a few per cent.
- Pressure variation over the stack height is neglected (about 1 % per 80 m): for very tall stacks, 300–500 m, both densities fall by 4–6 % at the top and the draught is overstated by roughly 2–3 %.
References
- ISO 2533:1975 (standard atmosphere)
- IUPAC atomic weights
- CODATA 2018 (gas constant)
Questions and answers
How is chimney draught calculated?
Draught = g × H × (ρ air − ρ gas). A 60 m stack with flue gas at 150 °C and air at 30 °C at sea level gives 177 Pa, about 18 mmWC, before friction and exit losses.
How does altitude change the draught?
Both densities fall with the site pressure. At 600 m the ISO 2533 pressure is 943 hPa, about 7 % below sea level, and the draught falls by the same share.
Is this the draught available at the boiler outlet?
No. It is the theoretical draught. The friction of the stack and flues and the velocity head at the exit take part of it; the available draught is what remains.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.