Worked example
Example: +20 K with 6 bar steam. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Wet flue gas flow | 110.00 t/h |
| Wet gas specific heat | 1.1000 kJ/(kg·K) |
| Reheat temperature rise | 20.000 K |
| Heating steam pressure (absolute) | 6.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reheat duty | 672.22 kW |
| Steam condensed | 1,160.3 kg/h |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_g c_p \Delta T, \quad \dot m_s = \frac{\dot Q}{h_{fg}(p_s)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_g\) | Wet flue gas flow | kg/s |
| \(c_p\) | Wet gas specific heat | J/(kg·K) |
| \(\Delta T\) | Reheat temperature rise | K |
| \(p_s\) | Heating steam pressure (absolute) | Pa |
| \(\dot Q\) | Reheat duty | W |
| \(\dot m_s\) | Steam condensed | kg/s |
Method and standards
Energy balance on the gas with a mean wet-gas specific heat; the steam condensed is the duty over the latent heat at the heating pressure (IAPWS-IF97).
Where it is used
- Scrubber stack design.
Common mistakes
- Using dry gas flow.
Assumptions and limits
- No droplets carried. Gas leaving a wet scrubber usually carries droplets that must be evaporated before its temperature rises; that heat can be large and is not included, so allow for it or use the mist eliminator maker's carry-over.
- Dry saturated heating steam in, saturated condensate out, no heater loss: superheat in the steam or subcooled condensate lowers the steam needed.
- The heating steam pressure is absolute.
References
- Energy balance; latent heat from IAPWS-IF97
Questions and answers
Why reheat?
Saturated gas condenses in the stack, corroding it and raining out droplets; reheat also helps buoyancy.
How much?
A rise of 15–30 K above saturation is common.
Alternatives?
Wet stack designs with liners and drains, or a gas–gas heater.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.