FireCADCalc

SO₂ Emission from Fuel Sulphur (mg/Nm³)

Uncontrolled SO₂ concentration in dry flue gas from the fuel's sulphur, analysis and excess air, at actual and reference O₂, for comparison with emission limits.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperBoilerStack and chimney

Inputs

Examples: Indian coal 0.5 % S, 25 % excess air, at 6 % O2Fuel oil 2 % S, 15 %, at 3 % O2Imported coal 0.8 % S, 20 %, at 6 % O2

Ultimate analysis, as fired, by mass

20.95 % is the physical value; EU IED Annex VI and Indian practice write 21 %, US EPA Method 19 uses 20.9 %. Enter the value of the rule you report against.

Results

All fuel sulphur is taken to leave as SO₂; sulphur retained in ash (notable with high-calcium ash or limestone) lowers it.

SO₂ at reference O₂, dry, normal1,538.1mg/Nm³
SO₂ at actual O₂, dry, normal1,786.4mg/Nm³
Actual O₂ in dry flue gas3.5863%
SO₂ per kg of fuel9.9903g/kg
Dry flue gas per kg of fuel5.5924Nm³/kg

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Indian coal 0.5 % S, 25 % excess air, at 6 % O2. The inputs, in the units selected above:

InputValue
Carbon45.000 %
Hydrogen3.5000 %
Oxygen5.0000 %
Nitrogen1.0000 %
Sulphur0.50000 %
Ash35.000 %
Moisture10.000 %
Excess air25.000 %
Air humidity (kg water per kg dry air)0.013000 kg/kg
Reference O₂ of the emission limit (dry)6.0000 %
O₂ in air used by the rule20.950 %

Applying the formula below gives:

ResultValue
SO₂ at reference O₂, dry, normal1,538.1 mg/Nm³
SO₂ at actual O₂, dry, normal1,713.1 mg/Nm³
Actual O₂ in dry flue gas4.2989 %
SO₂ per kg of fuel9.9903 g/kg
Dry flue gas per kg of fuel5.8317 Nm³/kg

Open this example in the calculator and change any input.

Formula

\(m_{SO_2} = S\,\frac{M_{SO_2}}{M_S} \qquad c = \frac{m_{SO_2}}{V_{dg}} \qquad c_{ref} = c\,\frac{O_{2,air} - O_{2,ref}}{O_{2,air} - O_2}\)

Variables

Symbol Meaning SI unit
\(C, H, O, N, S, A, M\) ultimate analysis as fired –
\(EA\) excess air –
\(\omega\) air humidity kg/kg
\(O_{2,ref}\) reference O₂ (dry) –
\(O_{2,air}\) O₂ in air used by the rule (20.95 % physical; 21 % EU IED and Indian practice; 20.9 % US EPA) –
\(c_{ref}\) SO₂ at reference O₂ kg/m³
\(c\) SO₂ at actual O₂ kg/m³
\(O_2\) actual O₂ in dry flue gas –
\(m_{SO_2}\) SO₂ per kg fuel kg/kg
\(V_{dg}\) dry flue gas per kg fuel at normal conditions m³/kg
\(M_{SO_2}, M_S\) molar masses kg/kmol

Method and standards

Exact-ratio combustion balance with all fuel sulphur as SO₂; dry gas volume at 0 °C and 101.325 kPa; O₂ correction to the reference.

Where it is used

  • Checking a fuel against SO₂ limits.
  • Sizing FGD or limestone injection.
  • Permit applications.

Common mistakes

  • Using wet gas volume against dry-basis limits.
  • Correcting to the wrong reference O₂ for the fuel.
  • Using air-dried sulphur with as-fired flue gas.

Assumptions and limits

  • All sulphur to SO₂ (SO₃ and ash retention neglected); complete combustion.

References

  • Stoichiometry S + O₂ → SO₂ with the exact-ratio flue gas balance

Questions and answers

How much SO₂ does 0.5 % sulphur coal give?

At 25 % excess air (enter 25 %; the page opens at 20 %) the dry flue gas holds 1713 mg/Nm³ of SO₂ at its actual 4.3 % O₂, or 1538 mg/Nm³ at the 6 % O₂ reference often used for coal.

Why correct to a reference O₂?

So that diluting the gas with air cannot meet a limit; limits are stated at a fixed O₂ for each fuel.

Is all the sulphur emitted?

This assumes so; some stays in alkaline ash, and limestone in a fluidised bed captures much more.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.