Worked example
Example: 250 to 150 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flue gas flow | 100.00 t/h |
| Gas specific heat | 1.1000 kJ/(kg·K) |
| Gas temperature | 250.00 °C |
| Target mixed temperature | 150.00 °C |
| Ambient air temperature | 30.000 °C |
| Air specific heat | 1.0060 kJ/(kg·K) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dilution air | 91.120 t/h |
| Air per kg of gas | 0.91120 kg/kg |
| Total gas after mixing | 191.12 t/h |
Open this example in the calculator and change any input.
Formula
\(\dot m_a = \frac{\dot m_g c_{p,g}(T_g - T_m)}{c_{p,a}(T_m - T_a)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_g\) | Flue gas flow | kg/s |
| \(c_{p,g}\) | Gas specific heat | J/(kg·K) |
| \(T_g\) | Gas temperature | K |
| \(T_m\) | Target mixed temperature | K |
| \(T_a\) | Ambient air temperature | K |
| \(c_{p,a}\) | Air specific heat | J/(kg·K) |
| \(\dot m_a\) | Dilution air | kg/s |
| \(\dot m_a/\dot m_g\) | Air per kg of gas | kg/kg |
| \(\dot m_t\) | Total gas after mixing | kg/s |
Method and standards
Energy balance between the gas cooling from \(T_g\) to \(T_m\) and the air warming from \(T_a\) to \(T_m\). The output is the mass flow; convert it to volume at the fan temperature with the gas density there.
Where it is used
- Filter protection design.
- Fan capacity checks.
Common mistakes
- Mixing temperatures in a ratio of volumes.
Assumptions and limits
- Constant specific heats: use the mean gas value between \(T_m\) and \(T_g\) and the mean air value between \(T_a\) and \(T_m\). From very hot gas (above about 1000 °C) the mean gas specific heat is noticeably higher than at the stack.
- A warning appears above 3 kg of air per kg of gas.
References
- Energy balance ṁ_a c_p
- a (T_m − T_a) = ṁ_g c_p
- g (T_g − T_m)
Questions and answers
When is dilution air used?
As emergency protection for filters or when water spray is not possible.
Cost?
More gas through the ID fan and filter; the fan may run out of capacity.
O₂ reading?
Dilution raises the O₂ downstream: correct emissions to reference O₂.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.