Worked example
Example: Fresh 2000 m³/h at 35 °C 60 % with return 8000 m³/h at 24 °C 50 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Stream 1 volume flow (at its own state) | 2,000.0 m³/h |
| Stream 1 dry bulb | 35.000 °C |
| Stream 1 relative humidity | 60.000 % |
| Stream 2 volume flow (at its own state) | 8,000.0 m³/h |
| Stream 2 dry bulb | 24.000 °C |
| Stream 2 relative humidity | 50.000 % |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mixed air dry bulb | 26.142 °C |
| Mixed air relative humidity | 54.802 % |
| Mixed air humidity ratio | 11.623 g/kg |
| Mixed air enthalpy per kg of dry air | 55.932 kJ/kg |
| Total dry-air mass flow | 11,578 kg/h |
| Share of stream 1 in the dry air | 19.128 % |
Open this example in the calculator and change any input.
Formula
\(\dot m_{da,i} = \frac{\dot V_i}{v_i} \qquad W_m = \frac{\sum \dot m_{da,i} W_i}{\sum \dot m_{da,i}} \qquad h_m = \frac{\sum \dot m_{da,i} h_i}{\sum \dot m_{da,i}}\)
\(t_m = \frac{h_m - 2\,501\,000\,W_m}{1006 + 1860\,W_m}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_1\) | stream 1 volume flow | m³/s |
| \(T_1\) | stream 1 dry bulb | K |
| \(\varphi_1\) | stream 1 RH | – |
| \(\dot V_2\) | stream 2 volume flow | m³/s |
| \(T_2\) | stream 2 dry bulb | K |
| \(\varphi_2\) | stream 2 RH | – |
| \(p\) | barometric pressure | Pa |
| \(T_m\) | mixed dry bulb (t_m in °C) | K |
| \(\varphi_m\) | mixed RH | – |
| \(W_m\) | mixed humidity ratio | kg/kg |
| \(h_m\) | mixed enthalpy | J/kg |
| \(\dot m_{da}\) | dry-air mass flow | kg/s |
| \(x_1\) | stream 1 share of dry air | – |
| \(v_i\) | specific volume per kg dry air | m³/kg |
Method and standards
Adiabatic mixing of moist air on a dry-air basis (ASHRAE Handbook—Fundamentals ch. 1); properties of each stream as in the psychrometric calculator.
Where it is used
- Fresh and return air in air-handling units.
- Combustion air mixing.
- Dryer exhaust recirculation.
Common mistakes
- Weighting by volume at different temperatures.
- Averaging RH.
- Ignoring fog when very cold air meets humid air.
Assumptions and limits
- Steady flow, no heat exchange with the duct; pressure the same for both streams.
References
- ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
- IAPWS-IF97 saturation pressure
Questions and answers
What is the mix of 2000 m³/h at 35 °C 60 % and 8000 m³/h at 24 °C 50 %?
26.1 °C, 54.8 % RH, 11.6 g/kg; stream 1 is 19.1 % of the dry air.
Can I average the temperatures by volume?
Roughly, but the correct weighting is dry-air mass, and enthalpy and moisture mix linearly, not temperature or RH.
Why can the mix be supersaturated?
Mixing very cold and warm humid air can cross the saturation line: fog forms.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.