Air-Side Economiser: Free-Cooling Hours from Weather Bins

Hours of full and partial free cooling with an air-side economiser from six weather bins of temperature and hours, the supply temperature and changeover limit.

Inputs

Examples: Six bins, supply 13 °C, changeover 24 °CCooler site

Bin 1

Bin 2

Bin 3

Bin 4

Bin 5

Bin 6

Results

Dry-bulb changeover; in humid climates an enthalpy limit cuts the partial hours. Bins from your weather file.

Full free cooling (outdoor at or below supply)600.00h
Partial free cooling (between supply and changeover)5,000.0h
Total hours in the bins8,760.0h
Share of hours with some free cooling63.927%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Six bins, supply 13 °C, changeover 24 °C. The inputs, in the units selected above:

InputValue
Bin 1: mean outdoor temperature8.0000 °C
Bin 1: hours600.00 h
Bin 2: mean outdoor temperature14.000 °C
Bin 2: hours1,300.0 h
Bin 3: mean outdoor temperature19.000 °C
Bin 3: hours1,700.0 h
Bin 4: mean outdoor temperature24.000 °C
Bin 4: hours2,000.0 h
Bin 5: mean outdoor temperature29.000 °C
Bin 5: hours2,100.0 h
Bin 6: mean outdoor temperature34.000 °C
Bin 6: hours1,060.0 h
Supply air temperature13.000 °C
Changeover limit (outdoor air no warmer than this)24.000 °C

Applying the formula below gives:

ResultValue
Full free cooling (outdoor at or below supply)600.00 h
Partial free cooling (between supply and changeover)5,000.0 h
Total hours in the bins8,760.0 h
Share of hours with some free cooling63.927 %

Open this example in the calculator and change any input.

Formula

\(t_f = \sum_{T_i \le T_s} t_i, \quad t_p = \sum_{T_s < T_i \le T_{co}} t_i\)

Variables

Symbol Meaning SI unit
\(T_{1}\) Bin 1: mean outdoor temperature K
\(t_{1}\) Bin 1: hours s
\(T_{2}\) Bin 2: mean outdoor temperature K
\(t_{2}\) Bin 2: hours s
\(T_{3}\) Bin 3: mean outdoor temperature K
\(t_{3}\) Bin 3: hours s
\(T_{4}\) Bin 4: mean outdoor temperature K
\(t_{4}\) Bin 4: hours s
\(T_{5}\) Bin 5: mean outdoor temperature K
\(t_{5}\) Bin 5: hours s
\(T_{6}\) Bin 6: mean outdoor temperature K
\(t_{6}\) Bin 6: hours s
\(T_s\) Supply air temperature K
\(T_{co}\) Changeover limit (outdoor air no warmer than this) K
\(t_f\) Full free cooling (outdoor at or below supply) s
\(t_p\) Partial free cooling (between supply and changeover) s
\(t\) Total hours in the bins s
\(x\) Share of hours with some free cooling -

Method and standards

Bin counting.

Where it is used

  • Control room and data room AHUs.
  • Energy-saving cases.

Common mistakes

  • Using monthly means.
  • Ignoring humidity.

Assumptions and limits

  • Bin mean temperatures; bins that add up to more than a year are flagged.

References

  • Bin method on dry-bulb temperature (ASHRAE Handbook—HVAC Applications, economisers)

Questions and answers

What do the default bins give?

600 h of full free cooling and 5,000 h of partial out of 8,760.

Why partial?

Outdoor air cooler than the changeover limit still saves cooling, though it must be cooled further.

Humid climates?

Use an enthalpy changeover or the latent load rises.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.