Worked example
Example: 40 °C, 25 % RH, 85 % pad, 10 000 m³/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Inlet dry bulb | 40.000 °C |
| Inlet relative humidity | 25.000 % |
| Saturation efficiency of the pad or washer | 85.000 % |
| Air flow (at the inlet state) | 10,000 m³/h |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Outlet dry bulb | 26.066 °C |
| Outlet relative humidity | 80.557 % |
| Inlet wet bulb | 23.607 °C |
| Outlet humidity ratio | 17.157 g/kg |
| Water evaporated | 62.149 kg/h |
Open this example in the calculator and change any input.
Formula
\(T_2 = T_1 - \varepsilon\,(T_1 - T_{wb}) \qquad h_2 = h_1 \qquad W_2 = \frac{h_1 - 1006\,t_2}{2\,501\,000 + 1860\,t_2} \qquad \dot m_w = \dot m_{da}(W_2 - W_1)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_1\) | inlet dry bulb | K |
| \(\varphi_1\) | inlet RH | – |
| \(\varepsilon\) | saturation efficiency | – |
| \(\dot V\) | air flow at inlet | m³/s |
| \(p\) | barometric pressure | Pa |
| \(T_2\) | outlet dry bulb (t_2 in °C) | K |
| \(\varphi_2\) | outlet RH | – |
| \(T_{wb}\) | inlet wet bulb | K |
| \(W_2\) | outlet humidity ratio | kg/kg |
| \(\dot m_w\) | water evaporated | kg/s |
| \(h_1\) | inlet enthalpy | J/kg |
| \(\dot m_{da}\) | dry-air flow | kg/s |
Method and standards
Direct evaporative cooling follows the wet-bulb line at nearly constant enthalpy; the saturation (wet-bulb) efficiency sets how close the outlet comes to the wet bulb. Moist-air relations from ASHRAE ch. 1.
Where it is used
- Turbine and engine inlet air cooling.
- Spot cooling in boiler houses and workshops.
- Pre-cooling condenser air.
Common mistakes
- Using RH instead of the wet bulb to judge cooling potential.
- Forgetting the humidity rise inside the space.
- No bleed-off: scaling of pads.
Assumptions and limits
- Constant enthalpy; pump heat and make-up water temperature neglected.
References
- ASHRAE Handbook—Fundamentals ch. 1 Psychrometrics
- IAPWS-IF97 saturation pressure
Questions and answers
How cold will a 40 °C, 25 % RH inlet get with an 85 % pad?
The wet bulb is 23.6 °C, so the air leaves at 26.1 °C and 80.6 % RH; 10 000 m³/h evaporates about 62 kg/h of water.
What limits evaporative cooling?
The inlet wet bulb: air cannot be cooled below it, so it works best in dry weather.
Why add make-up beyond evaporation?
Bleed-off controls salts in the sump; it is extra water, not cooling.