FireCADCalc

Cooling Tower Range, Approach and Effectiveness

Range, approach, effectiveness, liquid-to-gas ratio and heat rejected by a wet cooling tower from hot and cold water temperatures, wet bulb and flows.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperIAPWS-IF97 (water and steam)Condenser and cooling tower

Inputs

Examples: Power plant tower 41 to 32 °C, wet bulb 27 °CProcess tower 38 to 31 °C, wet bulb 26 °CDry climate 40 to 29 °C, wet bulb 22 °C

Results

Range9.0000K
Approach to wet bulb5.0000K
Effectiveness R/(R + A)64.286%
Liquid-to-gas ratio1.1111kg/kg
Heat rejected112.83MW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Power plant tower 41 to 32 °C, wet bulb 27 °C. The inputs, in the units selected above:

InputValue
Hot water temperature (to tower)41.000 °C
Cold water temperature (from basin)32.000 °C
Ambient wet-bulb temperature27.000 °C
Water flow1.0800e+07 kg/h
Dry air flow9,720,000 kg/h
Atmospheric pressure1.0132 bar

Applying the formula below gives:

ResultValue
Range9.0000 K
Approach to wet bulb5.0000 K
Effectiveness R/(R + A)64.286 %
Liquid-to-gas ratio1.1111 kg/kg
Heat rejected112.83 MW

Open this example in the calculator and change any input.

Formula

\(R = T_{hot} - T_{cold} \qquad A = T_{cold} - T_{wb} \qquad \varepsilon = \frac{R}{R + A} \qquad \frac{L}{G} \qquad \dot Q = L\,\left[h(T_{hot}) - h(T_{cold})\right]\)

Variables

Symbol Meaning SI unit
\(T_{hot}\) hot water temperature K
\(T_{cold}\) cold water temperature K
\(T_{wb}\) ambient wet-bulb temperature K
\(L\) water flow kg/s
\(G\) dry air flow kg/s
\(p\) atmospheric pressure Pa
\(R\) range K
\(A\) approach K
\(\varepsilon\) effectiveness –
\(L/G\) liquid-to-gas ratio kg/kg
\(\dot Q\) heat rejected W
\(h\) water enthalpy J/kg

Method and standards

Range, approach and effectiveness as defined in cooling-tower practice (CTI terms; the BEE energy audit guide calls effectiveness "efficiency"); heat from water enthalpy by FireCAD's IAPWS-IF97.

Where it is used

  • Cooling tower performance checks and energy audits.
  • Comparing towers and seasons on the same basis.
  • Spotting fill fouling or poor water distribution from a rising approach.

Common mistakes

  • Using dry-bulb instead of wet-bulb temperature.
  • Measuring the wet bulb close to the tower, in its own warm plume.
  • Judging a tower by range alone: range follows the load, approach shows the tower.

Assumptions and limits

  • Steady load; water loss by evaporation neglected in the heat balance.
  • The air flow is used only for L/G; there is no air-side heat balance, so an L/G the air cannot support is not detected. Use the Merkel calculator to check the tower can do the duty.

References

  • IAPWS R7-97(2012) IF97
  • CTI and BEE cooling tower performance terms

Questions and answers

What are range and approach?

Range is how much the tower cools the water; approach is how close the cold water gets to the wet bulb. Water from 41 to 32 °C with a 27 °C wet bulb has a 9 K range and 5 K approach.

How is cooling tower effectiveness calculated?

Range over range plus approach: 9 / (9 + 5) = 64.3 %. Energy audit guides call this the cooling tower efficiency; compare it with the tower's design value rather than a fixed figure.

Why can't the water reach the wet bulb?

The driving force falls to zero as the water nears the wet bulb, so the last few kelvin need an ever larger tower. Approaches below about 3 K are rarely economic.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.