Worked example
Example: 3,000 m³/h, 600 mm, 400 m, 12 m lift. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow | 3,000.0 m³/h |
| Pipe inside diameter | 600.00 mm |
| Equivalent pipe length (pipe plus fittings) | 400.00 m |
| Pipe roughness | 0.045000 mm |
| Static lift (basin level to distribution) | 12.000 m |
| Condenser water-side pressure drop | 60.000 kPa |
| Pressure needed at the distribution nozzles | 10.000 kPa |
| Pump efficiency | 82.000 % |
| Water density | 996.00 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pipe velocity | 2.9473 m/s |
| Darcy friction factor | 0.012265 |
| Pipe friction head | 3.6214 m |
| Total pump head | 22.788 m |
| Pump shaft power | 226.20 kW |
Open this example in the calculator and change any input.
Formula
\(H = H_s + f_D\frac{L_e}{D}\frac{V^2}{2g} + \frac{\Delta p_c + p_n}{\rho g}, \quad P = \frac{\rho gQH}{\eta}\)
\(V = \frac{4Q}{\pi D^2}, \quad Re = \frac{\rho V D}{\mu}, \quad \frac{1}{\sqrt{f_D}} = -2\log_{10}\left(\frac{\varepsilon/D}{3.7} + \frac{2.51}{Re\sqrt{f_D}}\right)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Water flow | m³/s |
| \(D\) | Pipe inside diameter | m |
| \(L_e\) | Equivalent pipe length (pipe plus fittings) | m |
| \(\varepsilon\) | Pipe roughness | m |
| \(H_s\) | Static lift (basin level to distribution) | m |
| \(\Delta p_c\) | Condenser water-side pressure drop | Pa |
| \(p_n\) | Pressure needed at the distribution nozzles | Pa |
| \(\eta\) | Pump efficiency | - |
| \(\rho\) | Water density | kg/m³ |
| \(V\) | Pipe velocity | m/s |
| \(f_D\) | Darcy friction factor | - |
| \(Re\) | Reynolds number | - |
| \(\mu\) | water viscosity, fixed at 0.8 mPa·s (about 30 °C) | Pa·s |
| \(g\) | standard gravity, 9.80665 | m/s² |
| \(H_f\) | Pipe friction head | m |
| \(H\) | Total pump head | m |
| \(P\) | Pump shaft power | W |
Method and standards
Darcy–Weisbach pipe friction with the Colebrook friction factor, plus the static lift and the condenser and nozzle pressure drops converted to head.
Where it is used
- Cooling water pump selection.
- Checking a circuit after adding a condenser.
Common mistakes
- Counting the return leg as lift in an open circuit.
- Ignoring condenser fouling margin.
Assumptions and limits
- Single-phase water at about 30 °C: the viscosity is fixed at 0.8 mPa·s whatever density is entered. For much colder or warmer water the Reynolds number, and slightly the friction, differ.
- Relative roughness ε/D up to 0.1, the range of the Colebrook equation; above it the input is rejected.
References
- Darcy–Weisbach with the Colebrook friction factor (FireCAD engine) and static and component heads (definitions)
Questions and answers
What makes up the head?
Static lift to the tower distribution, pipe and fitting friction, the condenser's water-side drop and the nozzle pressure.
What velocity is usual?
2–3 m/s in large cooling water mains.
What do the defaults give?
3,000 m³/h in 600 mm pipe, 400 m equivalent, 12 m lift: about 23 m head and 226 kW.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.