FireCADCalc

Cooling Tower Cycles of Concentration Limited by Water Chemistry

Highest cycles of concentration before silica, hardness, chloride or TDS reach their limits, with the blowdown and make-up at those cycles.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: 35 MW, silica-limitedHard water, hardness-limited

Results

Limited by calcium hardness. Limits depend on the treatment programme, pH and temperature; use the chemical supplier's values.

Allowed cycles of concentration5.0000
Limiting species (1 silica, 2 hardness, 3 chloride, 4 TDS)2.0000
Evaporation52.282t/h
Blowdown (including drift)13.071t/h
Make-up65.353t/h
Deliberate blowdown (total less drift)12.966t/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 35 MW, silica-limited. The inputs, in the units selected above:

InputValue
Heat rejected35.000 MW
Silica in make-up (mg/L)20.000 -
Silica limit in circulating water (mg/L)150.00 -
Calcium hardness in make-up (mg/L as CaCO₃)120.00 -
Calcium hardness limit (mg/L as CaCO₃)600.00 -
Chloride in make-up (mg/L)50.000 -
Chloride limit (mg/L)500.00 -
TDS in make-up (mg/L)400.00 -
TDS limit (mg/L)2,500.0 -
Latent heat of evaporation2,410.0 kJ/kg
Drift as a share of evaporation0.20000 %

Applying the formula below gives:

ResultValue
Allowed cycles of concentration5.0000
Limiting species (1 silica, 2 hardness, 3 chloride, 4 TDS)2.0000
Evaporation52.282 t/h
Blowdown (including drift)13.071 t/h
Make-up65.353 t/h
Deliberate blowdown (total less drift)12.966 t/h

Open this example in the calculator and change any input.

Formula

\(N = \min_i\frac{C_{i,max}}{C_{i,mu}}, \quad E = \frac{Q}{h_{fg}}, \quad B = \frac{E}{N - 1}, \quad M = E + B, \quad B_d = B - d\,E\)

Variables

Symbol Meaning SI unit
\(Q\) Heat rejected W
\(SiO_2\) Silica in make-up (mg/L) -
\(SiO_{2,max}\) Silica limit in circulating water (mg/L) -
\(CaH\) Calcium hardness in make-up (mg/L as CaCO₃) -
\(CaH_{max}\) Calcium hardness limit (mg/L as CaCO₃) -
\(Cl\) Chloride in make-up (mg/L) -
\(Cl_{max}\) Chloride limit (mg/L) -
\(TDS\) TDS in make-up (mg/L) -
\(TDS_{max}\) TDS limit (mg/L) -
\(h_{fg}\) Latent heat of evaporation J/kg
\(d\) Drift as a share of evaporation -
\(N\) Allowed cycles of concentration -
\(\text{limit}\) Limiting species (1 silica, 2 hardness, 3 chloride, 4 TDS) -
\(E\) Evaporation kg/s
\(B\) Blowdown (including drift) kg/s
\(M\) Make-up kg/s
\(B_d\) deliberate blowdown, total solids-removing loss less drift kg/s

Method and standards

Mass balance on dissolved solids.

Where it is used

  • Cooling water treatment programmes.
  • Water conservation studies.

Common mistakes

  • Ignoring drift and leaks as blowdown.
  • Using limits without pH and temperature context.

Assumptions and limits

  • Conservative species; all heat removed by evaporation, so evaporation, blowdown and make-up are higher (by about 18 % at the default) than in the cooling tower water balance calculator, which takes an evaporative share of 0.85.
  • Drift here is a share of evaporation; the water balance calculator takes it as a share of circulating flow.
  • The limiting species is shown as a number (1 silica, 2 hardness, 3 chloride, 4 TDS) and named in the note.

References

  • Cooling tower mass balances: N = C_circulating/C_make-up
  • B = E/(N − 1)

Questions and answers

Which limit usually governs?

It depends on the make-up water and the treatment: silica often governs high-silica waters, calcium hardness where scale inhibitors are weak. The default limits are illustrative; use your chemical supplier's values.

Why raise cycles?

Blowdown falls steeply: going from 3 to 6 cycles cuts blowdown by 60 %.

What do the defaults give?

Calcium hardness limits first, at 5 cycles (silica would allow 7.5): about 52 t/h evaporation for 35 MW and 13 t/h of blowdown.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.