Worked example
Example: 2400 m³/h, 19.05 mm x 0.71 mm tubes, 2 passes, 2 m/s, 8 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling water flow | 2,400.0 m³/h |
| Tube outside diameter | 19.050 mm |
| Tube wall thickness | 0.71000 mm |
| Number of water passes | 2.0000 - |
| Design water velocity in the tubes | 2.0000 m/s |
| Effective tube length | 8.0000 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Tubes per pass | 1,366.0 |
| Total tubes | 2,732.0 |
| Actual water velocity | 1.9992 m/s |
| Tube inside diameter | 17.630 mm |
| Outside tube surface | 1,308.0 m² |
Open this example in the calculator and change any input.
Formula
\(d_i = d_o - 2\,t_w \qquad n_p = \left\lceil \frac{\dot V}{v \cdot \pi d_i^2/4} \right\rceil \qquad n = n_p\,N_p\)
\(v_{act} = \frac{\dot V}{n_p\,\pi d_i^2/4} \qquad A_o = n\,\pi\,d_o\,L\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | cooling water flow | m³/s |
| \(d_o\) | tube outside diameter | m |
| \(t_w\) | tube wall thickness | m |
| \(N_p\) | number of water passes | – |
| \(v\) | design water velocity | m/s |
| \(L\) | effective tube length | m |
| \(n_p\) | tubes per pass | – |
| \(n\) | total tubes | – |
| \(v_{act}\) | actual water velocity | m/s |
| \(d_i\) | tube inside diameter | m |
| \(A_o\) | outside tube surface | m² |
Method and standards
Continuity: every pass carries the whole flow, so tubes per pass follow from flow, velocity and the tube bore, rounded up to a whole tube.
Where it is used
- Laying out surface condensers, oil coolers and other shell-and-tube coolers.
- Checking tube velocity after a change of cooling water flow.
- Estimating the tube sheet size and number of tubes to buy.
Common mistakes
- Using the outside diameter for the flow area.
- Forgetting plugged tubes, which raise the velocity in the others.
- Counting each pass's tubes as carrying part of the flow.
Assumptions and limits
- Equal flow in all tubes; straight tubes; plugging margin not included: add spare tubes for the plugging you expect.
- The actual velocity is not checked against a limit; the 1.5–2.5 m/s range in the help is common design practice, and the tube maker sets the limit for the material.
References
- Continuity equation (flow = velocity × area)
Questions and answers
How many tubes does a condenser need?
Enough per pass to carry the water at the design velocity. 2400 m³/h at 2 m/s in 19.05 × 0.71 mm tubes needs 1366 tubes per pass; with two passes that is 2732 tubes and, 8 m long, 1308 m² of outside surface.
What water velocity is right?
Usually 1.5–2.5 m/s. Lower velocities let silt and scale settle; higher ones erode the tube inlets and raise pumping power. The tube material sets the limit.
Does the area match the required area?
Compare the outside surface here with the area from the condenser surface area calculator; adjust length or tube count until both agree.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.