Worked example
Example: Oil cooler 500 kW, 32 to 40 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Heat duty to remove | 500.00 kW |
| Cooling water inlet temperature | 32.000 °C |
| Cooling water outlet temperature | 40.000 °C |
| Water pressure (absolute) | 3.0000 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cooling water mass flow | 53,849 kg/h |
| Cooling water volume flow (at inlet) | 54.113 m³/h |
| Mean specific heat of the water | 4.1784 kJ/(kg·K) |
Open this example in the calculator and change any input.
Formula
\(\dot m = \frac{\dot Q}{h(p, T_2) - h(p, T_1)} \qquad \dot V = \frac{\dot m}{\rho(p, T_1)} \qquad \bar c_p = \frac{h(T_2) - h(T_1)}{T_2 - T_1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | heat duty | W |
| \(T_1\) | water inlet temperature | K |
| \(T_2\) | water outlet temperature | K |
| \(p\) | water pressure, absolute | Pa |
| \(\dot m\) | water mass flow | kg/s |
| \(\dot V\) | water volume flow at inlet | m³/s |
| \(\bar c_p\) | mean specific heat | J/(kg·K) |
| \(h\) | water enthalpy | J/kg |
| \(\rho\) | water density | kg/m³ |
Method and standards
Energy balance with water enthalpy and density from FireCAD's IAPWS-IF97.
Where it is used
- Sizing cooling water for condensers, oil coolers, compressor intercoolers and process coolers.
- Cooling water pump and pipe sizing.
- Cooling tower load totals.
Common mistakes
- Mixing kW and kcal/h, or m³/h and kg/s.
- Using a design temperature rise that the cooling tower cannot deliver in summer.
- Forgetting fouling margins on the cooler, not on the water flow.
Assumptions and limits
- Water stays liquid; no heat loss to surroundings.
References
- IAPWS R7-97(2012) IF97
- first law of thermodynamics
Questions and answers
How much cooling water does a heat load need?
Heat duty divided by the water's enthalpy rise. A 500 kW oil cooler with water from 32 to 40 °C needs 14.96 kg/s, about 54 m³/h; the mean specific heat is 4.178 kJ/(kg·K).
Can I just use 4.186 kJ/(kg·K)?
Near room temperature the difference is under 0.5 %. This calculator uses the IF97 enthalpy at the actual temperatures and pressure, which stays right for hot water too.
How do I pick the temperature rise?
From the cooler design and the cooling tower: 5–10 K is common. A larger rise needs less water but a larger cooler.