Worked example
Example: Feedwater 51 t/h at 105 °C, 90 bar(a), 2.5 m/s, check DN80 (77.9 mm). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow | 51,000 kg/h |
| Water pressure (absolute) | 90.000 bar |
| Water temperature | 105.00 °C |
| Design velocity | 2.5000 m/s |
| Chosen pipe inside diameter to check (0 = skip) | 77.900 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Inside diameter for the design velocity | 86.744 mm |
| Velocity in the chosen pipe | 3.0998 m/s |
| Volume flow | 53.187 m³/h |
| Water density | 958.88 kg/m³ |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{\dot m}{\rho} \qquad D = \sqrt{\frac{4\,Q}{\pi\,u}} \qquad u_{sel} = \frac{4\,Q}{\pi\,D_{sel}^2}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | water flow | kg/s |
| \(p\) | water pressure, absolute | Pa |
| \(T\) | water temperature | K |
| \(u\) | design velocity | m/s |
| \(D_{sel}\) | chosen pipe inside diameter | m |
| \(D\) | inside diameter for the design velocity | m |
| \(u_{sel}\) | velocity in the chosen pipe | m/s |
| \(Q\) | volume flow | m³/s |
| \(\rho\) | water density | kg/m³ |
Method and standards
Continuity for a full circular pipe with the liquid density from FireCAD's IAPWS-IF97 implementation.
Where it is used
- Sizing feedwater, cooling water and make-up water lines.
- Pump suction and discharge line selection.
- Checking existing lines after a flow increase.
Common mistakes
- Using the same velocity for suction and discharge: suction needs lower velocity.
- Ignoring hot-water density and viscosity.
- Selecting by velocity alone on long lines.
Assumptions and limits
The water must be liquid below its saturation temperature at the pressure entered. Flashing condensate is two-phase and is not covered. At exactly saturation the IF97 phase test may treat the state as vapour and reject it: enter a pressure slightly above the saturation pressure for saturated condensate.
Liquid water only (the pressure must be above the saturation pressure).
Sizing by velocity; check the pressure drop and, for pump suction lines, NPSH.
References
- IAPWS R7-97(2012) IF97 (density)
- Continuity equation
Questions and answers
How do I size a feedwater pipe?
Volume flow = mass flow ÷ density; area = volume flow ÷ velocity. 51 t/h at 105 °C is 53.2 m³/h; at 2.5 m/s it needs an 87 mm bore. A DN80 pipe (77.9 mm) would run at 3.1 m/s.
Why enter the mass flow?
Boiler balances are in mass. Hot water is lighter (959 kg/m³ at 105 °C), so the same mass needs about 4 % more volume than cold water.
Does this cover condensate with flash steam?
No. Condensate lines after steam traps carry flash steam and need a two-phase method; this is for liquid lines.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.