Worked example
Example: DN150 (168.3 x 7.11) water-filled, 100 N/m insulation, simply supported. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe outside diameter | 168.30 mm |
| Wall thickness (less corrosion allowance if you wish) | 7.1100 mm |
| Pipe material density | 7,850.0 kg/m³ |
| Contents density (0 for gas) | 1,000.0 kg/m³ |
| Insulation, cladding and other weight per length | 100.00 N/m |
| Modulus of elasticity | 200.00 GPa |
| Allowed bending stress from weight (your design value) | 40.000 MPa |
| Allowed sag at mid-span | 2.5000 mm |
| Treat the span as | Simply supported (wL²/8, 5wL⁴/384EI) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total weight per length | 560.02 N/m |
| Second moment of area of the pipe | 1,171.6 cm⁴ |
| Section modulus of the pipe | 139.23 cm³ |
| Span limited by stress | 8.9195 m |
| Span limited by sag | 5.3239 m |
| Largest span (the smaller of the two) | 5.3239 m |
Open this example in the calculator and change any input.
Formula
\(w = g\left[\rho_p \tfrac{\pi}{4}(D_o^2 - d_i^2) + \rho_f \tfrac{\pi}{4} d_i^2\right] + w_x\)
\(L_s = \sqrt{\frac{k_m Z S_b}{w}}, \quad L_d = \left(\frac{k_d E I y}{w}\right)^{1/4}, \quad L = \min(L_s, L_d)\)
\(k_m = 8,\ k_d = 384/5\ (\text{simply supported}); \quad k_m = 12,\ k_d = 384\ (\text{fixed})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_o\) | Pipe outside diameter | m |
| \(t\) | Wall thickness (less corrosion allowance if you wish) | m |
| \(\rho_p\) | Pipe material density | kg/m³ |
| \(\rho_f\) | Contents density (0 for gas) | kg/m³ |
| \(w_x\) | Insulation, cladding and other weight per length | N/m |
| \(E\) | Modulus of elasticity | Pa |
| \(S_b\) | Allowed bending stress from weight (your design value) | Pa |
| \(y\) | Allowed sag at mid-span | m |
| \(\text{ends}\) | Treat the span as | - |
| \(w\) | Total weight per length | N/m |
| \(I\) | Second moment of area of the pipe | m⁴ |
| \(Z\) | Section modulus of the pipe | m³ |
| \(L_s\) | Span limited by stress | m |
| \(L_d\) | Span limited by sag | m |
| \(L\) | Largest span (the smaller of the two) | m |
| \(d_i\) | Pipe inside diameter | m |
| \(g\) | Standard gravity | m/s² |
| \(k_m, k_d\) | Beam coefficients for moment and sag | - |
Method and standards
The pipe is a uniformly loaded beam; the span is the smaller of the one that reaches the allowed bending stress and the one that reaches the allowed mid-span sag.
Where it is used
- Laying out supports on racks and in plant rooms.
- Checking spans after adding insulation or changing contents.
- Quick checks where no code table applies.
Common mistakes
- Forgetting the insulation and contents.
- Using the same span next to valves and bends.
- Ignoring the code's span table where it has one.
Assumptions and limits
- Straight horizontal run, uniform weight.
- Weight only: no wind, seismic or thermal loads.
- A real continuous pipe lies between the simply supported and fixed-end cases; simply supported is the safe side. Concentrated loads (valves, flanges) are not included.
References
- Beam theory for uniform load (simply supported and fixed-end)
- Allowed stress and sag set by the designer
Questions and answers
What span suits a water-filled DN150 pipe?
With 100 N/m of insulation it weighs 560 N/m; 40 MPa bending allows 8.9 m but 2.5 mm sag allows only 5.3 m simply supported, so sag governs.
Why two limits?
Stress protects the pipe; sag keeps drainage and avoids pockets and vibration. Small pipes are usually sag-limited.
Simply supported or fixed?
A continuous pipe lies between the two; simply supported is the safe side.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.