Worked example
Example: Steel DN200, 6 mm wall, 2 m/s stopped, 500 m, 0.5 s closure. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Bulk modulus of the liquid | 2.2000 GPa |
| Liquid density | 998.00 kg/m³ |
| Pipe inside diameter | 200.00 mm |
| Pipe wall thickness | 6.0000 mm |
| Young's modulus of the pipe wall | 200.00 GPa |
| Change in flow velocity | 2.0000 m/s |
| Pipe length from the valve to the reservoir or tank | 500.00 m |
| Valve closing time | 0.50000 s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Pressure wave speed | 1,270.0 m/s |
| Pressure rise for rapid closure (Joukowsky) | 25.350 bar |
| Head rise for rapid closure | 259.01 m |
| Critical closing time (wave round trip) | 0.78738 s |
| Pressure rise for the given closing time | 25.350 bar |
Open this example in the calculator and change any input.
Formula
\(a = \sqrt{\frac{K/\rho}{1 + \frac{K D}{E e}}}\)
\(\Delta p = \rho\, a\, \Delta v, \quad \Delta H = \frac{\Delta p}{\rho g}\)
\(2L/a, \quad \Delta p_c = \frac{2 \rho L \Delta v}{t_c} \ \text{for}\ t_c > 2L/a\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(K\) | liquid bulk modulus | Pa |
| \(\rho\) | liquid density | kg/m³ |
| \(D\) | pipe inside diameter | m |
| \(e\) | wall thickness | m |
| \(E\) | Young's modulus of the pipe | Pa |
| \(\Delta v\) | change in velocity | m/s |
| \(L\) | pipe length | m |
| \(t_c\) | valve closing time | s |
| \(a\) | wave speed | m/s |
| \(\Delta p\) | pressure rise, rapid closure | Pa |
| \(\Delta H\) | head rise | m |
| \(2L/a\) | critical closing time | s |
| \(\Delta p_c\) | pressure rise for the closing time | Pa |
| \(g\) | standard gravity | m/s² |
Method and standards
Stopping a liquid column sends a pressure wave along the pipe at speed a, set by the liquid's compressibility and the pipe wall's elasticity (Korteweg). The Joukowsky rise ρ a Δv applies to closures faster than the wave's round trip 2L/a; slower closures are estimated by Michaud's relation.
Where it is used
- Setting valve closing times on pump discharges and long lines.
- Checking pipe pressure ratings against pump trips.
- Deciding when surge vessels or slow-closing check valves are needed.
Common mistakes
- Ignoring the surge from a pump trip, which stops the flow as fast as a valve.
- Using closure time from fully open; most of the flow is cut in the last part of travel.
- Forgetting vapour-cavity collapse can exceed the Joukowsky value.
Assumptions and limits
- Single uniform pipe, thin wall, anchored with expansion joints (restraint factor 1 in the Korteweg wave speed). A pipe anchored against axial movement or buried has a factor below 1 (about 1 − ν² for a fully anchored pipe), which gives a slightly higher wave speed and surge.
- Column separation is not checked: when the downstream or low-pressure side of a closure falls to vapour pressure, the cavity's collapse can give a surge above the Joukowsky value.
- Friction and cavitation not included; complex systems need a transient analysis.
References
- Joukowsky (1898)
- Korteweg wave speed
- Michaud slow-closure relation
Questions and answers
How much pressure rise does stopping 2 m/s of water give?
In a DN200 steel pipe with 6 mm wall the wave speed is about 1 270 m/s, so the rise is about 25 bar (259 m of head).
How slow must a valve close to avoid it?
Slower than 2L/a, the wave's round trip: 0.79 s for 500 m in the example. Closing in 10 s cuts the rise to about 2 bar.
Why are plastic pipes gentler?
Their low modulus slows the pressure wave, so the same velocity change gives a much smaller surge.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.