Worked example
Example: 20 t/h at 0.2 bar(a), 92 % dry, air 35 to 52 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Exhaust steam flow | 20,000 kg/h |
| Exhaust steam dryness fraction | 92.000 % |
| Condenser pressure (absolute) | 20.000 kPa |
| Ambient air temperature | 35.000 °C |
| Air temperature leaving the bundles | 52.000 °C |
| Atmospheric pressure | 1.0132 bar |
Applying the formula below gives:
| Result | Value |
|---|---|
| Condenser heat load | 12.050 MW |
| Air mass flow (dry air) | 2,536,928 kg/h |
| Air volume flow at ambient (dry air) | 2,214,619 m³/h |
| Initial temperature difference | 25.059 K |
| Condensing temperature | 60.059 °C |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_s\,\left[h(p_c, x) - h_f(p_c)\right] \qquad \dot m_a = \frac{\dot Q}{h_a(T_{a,2}) - h_a(T_{a,1})}\)
\(\dot V_a = \frac{\dot m_a}{\rho_a},\quad \rho_a = \frac{p_{atm}\,M_{da}}{R\,T_{a,1}} \qquad ITD = T_{sat} - T_{a,1}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_s\) | exhaust steam flow | kg/s |
| \(x\) | exhaust steam dryness | – |
| \(p_c\) | condenser pressure, absolute | Pa |
| \(T_{a,1}\) | ambient air temperature | K |
| \(T_{a,2}\) | air temperature leaving the bundles | K |
| \(p_{atm}\) | atmospheric pressure | Pa |
| \(\dot Q\) | condenser heat load | W |
| \(\dot m_a\) | air mass flow | kg/s |
| \(\dot V_a\) | air volume flow at ambient | m³/s |
| \(ITD\) | initial temperature difference | K |
| \(T_{sat}\) | condensing temperature | K |
| \(h\), \(h_f\) | steam and saturated liquid enthalpy | J/kg |
| \(h_a\) | dry air enthalpy (Shomate) | J/kg |
| \(\rho_a\) | air density at ambient | kg/m³ |
| \(M_{da}\) | molar mass of dry air | kg/kmol |
| \(R\) | universal gas constant | J/(kmol·K) |
Method and standards
Steam-side energy balance with FireCAD's IAPWS-IF97; air-side enthalpy from NIST Shomate heat capacities of dry air; air density by the ideal-gas law at ambient.
Where it is used
- Sizing ACCs and their fans for plants without enough water.
- Checking summer back pressure of an existing ACC.
- Comparing wet and dry cooling at the concept stage.
Common mistakes
- Designing on the average temperature instead of the hot-day temperature.
- Ignoring hot-air recirculation, which raises the effective inlet temperature.
- Forgetting site altitude in the air density.
Assumptions and limits
- Dry air (humidity neglected on the air side): the air flows are dry-air values; on hot humid days the real volume flow is slightly larger.
- Condensate leaves saturated (no subcooling); no air in-leakage on the steam side; fan heat is not added to the duty.
- The ITD is reported for comparison only; the condenser pressure is an input, not checked against the ITD the bundles can achieve.
- Dry air enthalpy by Shomate; below 25 °C the CO₂ and Ar terms are extrapolated slightly, a negligible effect for trace species.
References
- IAPWS R7-97(2012) IF97
- NIST Chemistry WebBook Shomate equations (air)
Questions and answers
How much air does an air-cooled condenser need?
Heat load divided by the air's enthalpy rise. 20 t/h of 92 % dry steam at 0.2 bar(a) gives 12.0 MW; air heated from 35 to 52 °C must flow at 705 kg/s, about 615 m³/s at ambient.
What is ITD?
The initial temperature difference: condensing temperature minus ambient air temperature, 25 K here. ACCs are sized on ITD; a hot day lowers it and raises the turbine back pressure.
Why do ACC plants run at higher back pressure?
Air is a poorer coolant than water and the dry bulb is above the wet bulb, so condensing temperatures of 50–65 °C are common, against 40–48 °C with wet cooling.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.