Worked example
Example: FD fan 20 m³/s, 300 mmWC, fan 82 %, direct drive, motor 95 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume flow at the fan inlet | 72,000 m³/h |
| Fan pressure rise (total, or static with a static efficiency) | 300.00 mmWC |
| Fan efficiency | 82.000 % |
| Drive efficiency (coupling, belt, gearbox) | 100.00 % |
| Motor efficiency | 95.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fan shaft power | 71.756 kW |
| Motor output power (at the motor shaft) | 71.756 kW |
| Electrical input power | 75.533 kW |
| Air power | 58.840 kW |
| Overall efficiency, wire to air | 77.900 % |
Open this example in the calculator and change any input.
Formula
\(P_a = \dot V\,\Delta p_t \qquad P_s = \frac{P_a}{\eta_f} \qquad P_m = \frac{P_s}{\eta_d} \qquad P_e = \frac{P_m}{\eta_m} \qquad \eta = \eta_f\,\eta_d\,\eta_m\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | volume flow at the fan inlet | m³/s |
| \(\Delta p_t\) | fan pressure rise (total or static, matching the efficiency) | Pa |
| \(\eta_f\) | fan efficiency | – |
| \(\eta_d\) | drive efficiency (coupling, belt, gearbox) | – |
| \(\eta_m\) | motor efficiency | – |
| \(P_a\) | air power | W |
| \(P_s\) | fan shaft power | W |
| \(P_m\) | motor output power | W |
| \(P_e\) | electrical input power | W |
| \(\eta\) | overall efficiency, wire to air | – |
Method and standards
Definitions of fan air power and fan efficiency of ISO 5801 (and AMCA 210), for incompressible flow: the air power is the product of the inlet volume flow and the fan pressure. Shaft, motor and electrical power follow by dividing by the efficiencies in turn.
Where it is used
- Sizing FD, ID, PA and SA fan motors.
- Energy audits of fans and blowers.
- Comparing damper and speed control.
Common mistakes
- Using total pressure with a static-pressure efficiency, or the reverse.
- Ignoring gas density: an ID fan at 150 °C moves lighter gas than air at 20 °C.
- Adding margins on flow and pressure and then again on power.
Assumptions and limits
- Incompressible: below about 2.5 kPa pressure rise the error is under 1 %; above it ISO 5801's compressibility coefficient lowers the power by a few per cent.
- Volume flow at the fan inlet temperature and pressure, not normal volume.
- The result is the power absorbed at this duty; the motor rating needs the margin your standard or the fan maker requires.
References
- ISO 5801 (fan power and efficiency definitions)
- AMCA 210
Questions and answers
How do I calculate fan power?
Air power = volume flow × pressure rise. A fan moving 20 m³/s against 300 mmWC (2 942 Pa) delivers 58.8 kW to the air; at 82 % fan efficiency the shaft power is 71.8 kW, and with a 95 % motor the input is 75.5 kW.
Static or total pressure?
Either, as long as the efficiency is on the same basis. Fan total pressure goes with total efficiency, fan static pressure with static efficiency (ISO 5801).
Does gas density matter?
Not directly. The power depends on the actual volume flow at the fan inlet and the pressure rise; density changes both of these for a given mass flow, which is why hot ID fans need more power per kg than FD fans.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.