Worked example
Example: FD fan 3 kPa, 1.15 kg/m³, 80 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fan total pressure rise | 305.91 mmWC |
| Gas density at the inlet | 1.1500 kg/m³ |
| Specific heat of the gas | 1.0060 kJ/(kg·K) |
| Fan efficiency | 80.000 % |
| Inlet temperature | 35.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Temperature rise through the fan | 3.2414 K |
| Outlet temperature | 38.241 °C |
Open this example in the calculator and change any input.
Formula
\(\Delta T = \frac{\Delta p}{\rho\,c_p\,\eta_f} \qquad T_2 = T_1 + \Delta T\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\Delta p\) | fan total pressure rise | Pa |
| \(\rho\) | gas density at the inlet | kg/m³ |
| \(c_p\) | specific heat of the gas | J/(kg·K) |
| \(\eta_f\) | fan efficiency | – |
| \(T_1\) | inlet temperature | K |
| \(\Delta T\) | temperature rise | K |
| \(T_2\) | outlet temperature | K |
Method and standards
Energy balance on the fan: all the shaft power ends up in the gas, as useful pressure rise and as heat from the losses. With air power \(\dot V\Delta p\) and shaft power \(\dot V\Delta p/\eta\), the gas gains \(\Delta p/(\rho\eta)\) per kg.
Where it is used
- Checking gas temperature after fans.
- Energy balance of recirculation fans.
- Explaining temperature rise across a fan.
Common mistakes
- Treating fan heat as a loss when it goes into the gas.
- Using total pressure with static efficiency.
- Forgetting motor heat for in-stream motors.
Assumptions and limits
- Adiabatic fan casing; bearing losses outside the gas stream are included (conservative).
- Incompressible; for blowers above about 20 kPa use the isentropic relation instead (flagged).
References
- Energy balance on the fan (ISO 5801 power definitions)
Questions and answers
How much does a fan heat the air?
ΔT = Δp/(ρ·c_p·η). An FD fan at 3 kPa and 80 % warms air by about 3 K; a PA fan at 12 kPa by about 13 K.
Why does it matter?
The warmer air needs more volume downstream and changes the air heater duty; for high-pressure blowers the outlet temperature can limit duct and seal materials.
Which pressure do I use?
The fan total pressure rise with the total efficiency.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.