FireCADCalc

Fan Density Correction (Site to Standard Air)

Converts a fan duty at site temperature and altitude to standard air and back: pressure and power scale with density at the same speed and volume flow.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationThermic fluid heatingFan and blower

Inputs

Examples: FD fan at 40 °C and 600 m to standard air 1.2 kg/m³ID fan, flue gas 150 °C, M 30, sea levelHot air at 250 °C, 0.98 bar

Dry air 28.97; flue gas about 30 (coal, oil) or 27.5–28.5 (natural gas).
1.2 kg/m³ is standard air in AMCA 210 and fan catalogues (20 °C, 101.325 kPa, 50 % humidity).

Altitude (ISO 2533 standard atmosphere)

Barometric pressure entered

Results

Fan pressure at standard density325.67mmWC
Shaft power at standard density79.843kW
Density ratio standard / site1.0646
Gas density at site conditions1.1272kg/m³
Mass flow of standard air at the same volume86,400kg/h
Barometric pressure used1.0132bar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: FD fan at 40 °C and 600 m to standard air 1.2 kg/m³. The inputs, in the units selected above:

InputValue
Volume flow at the fan inlet72,000 m³/h
Fan pressure at site conditions305.91 mmWC
Shaft power at site conditions75.000 kW
Gas temperature at the fan inlet40.000 °C
Molar mass of the gas28.966 kg/kmol
Site pressure fromAltitude (ISO 2533 standard atmosphere)
Site altitude above sea level600.00 m
Barometric pressure at the site (absolute)1.0132 bar
Standard (test) density1.2000 kg/m³

Applying the formula below gives:

ResultValue
Fan pressure at standard density349.84 mmWC
Shaft power at standard density85.769 kW
Density ratio standard / site1.1436
Gas density at site conditions1.0493 kg/m³
Mass flow of standard air at the same volume86,400 kg/h
Barometric pressure used0.94322 bar

Open this example in the calculator and change any input.

Formula

\(\rho = \frac{p\,M}{R\,T} \qquad k = \frac{\rho_0}{\rho} \qquad \Delta p_0 = k\,\Delta p \qquad P_0 = k\,P \qquad \dot m_0 = \rho_0\,\dot V\)

Variables

Symbol Meaning SI unit
\(\dot V\) volume flow at the fan inlet m³/s
\(\Delta p\) fan pressure at site conditions Pa
\(P\) shaft power at site conditions W
\(T\) gas temperature at the fan inlet K
\(M\) molar mass of the gas kg/kmol
\(\text{site}\) site pressure from altitude or entered –
\(z\) site altitude m
\(p_s\) barometric pressure entered Pa
\(\rho_0\) standard (test) density kg/m³
\(\Delta p_0\) fan pressure at standard density Pa
\(P_0\) shaft power at standard density W
\(\rho_0/\rho\) density ratio –
\(\rho\) gas density at site kg/m³
\(\dot m_0\) mass flow of standard air at the same volume kg/s
\(p\) barometric pressure used Pa
\(R\) universal gas constant J/(mol·K)

Method and standards

Fan laws of AMCA Publication 99 at constant speed and size: pressure and power in proportion to density, volume flow unchanged. Standard air of 1.2 kg/m³ as in AMCA 210; site pressure from ISO 2533; ideal-gas density.

Where it is used

  • Correcting fan ratings to site gas temperature and altitude.
  • Choosing fan motors for cold start.
  • Comparing fan tests at different conditions.

Common mistakes

  • Forgetting the cold-start case for hot-gas fans.
  • Using sea-level density at a hill site.
  • Correcting volume flow, which does not change with density for a given speed.

Assumptions and limits

  • Same fan, same speed, same point of rating.
  • Inlet suction is neglected in the density; for an ID fan with a large suction, enter the inlet absolute pressure as the barometric pressure.
  • Compressibility neglected.

References

  • AMCA 99 (fan laws)
  • AMCA 210 (standard air 1.2 kg/m³)
  • ISO 2533 (site pressure)

Questions and answers

How do I read a fan catalogue for hot gas?

Catalogues are for standard air (1.2 kg/m³). At the same speed and volume flow, pressure and power scale with density. An ID fan duty of 2.5 kPa on flue gas at 150 °C is 3.47 kPa in standard air: look it up in the catalogue at that pressure.

Does the volume flow change?

No. A fan at a given speed moves the same volume whatever the density; the mass flow changes.

What about altitude?

The site pressure lowers the density in the same way: at 600 m and 40 °C air is 1.05 kg/m³, so a catalogue fan delivers 12.5 % less pressure at site.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.