FireCADCalc

Langelier and Ryznar Index (LSI, RSI) of Water

Langelier saturation index and Ryznar stability index of cooling, boiler feed or process water from pH, temperature, TDS, calcium hardness and alkalinity.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserCondenser and cooling towerWater treatment plant

Inputs

Examples: Cooling water 25 °C, pH 8.0, TDS 500, Ca 250, alkalinity 100 mg/LCooling tower basin 40 °C, pH 8.4, TDS 1 500, Ca 400, alkalinity 200RO permeate 20 °C, pH 6.8, TDS 50, Ca 20, alkalinity 15

Results

LSI above zero: the water tends to deposit calcium carbonate scale.

RSI above about 7: in common reading, a corrosive water.

Both indices describe the tendency only; inhibitors, temperature at the heat transfer surface and flow change what really happens.

Saturation pH (calcium carbonate)7.5602
Langelier saturation index0.43976
Ryznar stability index7.1205
Factor A (dissolved solids)0.16990
Factor B (temperature)2.0883
Factor C (calcium)1.9979
Factor D (alkalinity)2.0000

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Cooling water 25 °C, pH 8.0, TDS 500, Ca 250, alkalinity 100 mg/L. The inputs, in the units selected above:

InputValue
Measured pH of the water8.0000 -
Water temperature25.000 °C
Total dissolved solids500.00 mg/L
Calcium hardness as CaCO₃250.00 mg/L
Total (M) alkalinity as CaCO₃100.00 mg/L

Applying the formula below gives:

ResultValue
Saturation pH (calcium carbonate)7.5602
Langelier saturation index0.43976
Ryznar stability index7.1205
Factor A (dissolved solids)0.16990
Factor B (temperature)2.0883
Factor C (calcium)1.9979
Factor D (alkalinity)2.0000

Open this example in the calculator and change any input.

Formula

\(pH_s = (9.3 + A + B) - (C + D)\)

\(A = \frac{\log_{10}\text{TDS} - 1}{10}, \quad B = -13.12 \log_{10}(t + 273) + 34.55\)

\(C = \log_{10}\text{Ca} - 0.4, \quad D = \log_{10}\text{Alk}\)

\(LSI = pH - pH_s, \quad RSI = 2\,pH_s - pH\)

Variables

Symbol Meaning SI unit
\(pH\) Measured pH of the water -
\(T\) Water temperature K
\(\text{TDS}\) Total dissolved solids kg/m³
\(\text{Ca}\) Calcium hardness as CaCO₃ kg/m³
\(\text{Alk}\) Total (M) alkalinity as CaCO₃ kg/m³
\(pH_s\) Saturation pH (calcium carbonate) -
\(LSI\) Langelier saturation index -
\(RSI\) Ryznar stability index -
\(A\) Factor A (dissolved solids) -
\(B\) Factor B (temperature) -
\(C\) Factor C (calcium) -
\(D\) Factor D (alkalinity) -

Method and standards

The saturation pH pHs is the pH at which the water would be just saturated with calcium carbonate. The working form above, with TDS, calcium hardness and total alkalinity in mg/L (the last two as CaCO₃) and temperature t in °C, is the one used in water-treatment practice for Langelier's equilibrium. Ryznar's index weights the same pHs to separate scaling from corrosive waters more clearly.

Where it is used

  • Cooling tower chemistry: setting cycles of concentration and acid dosing.
  • Checking whether softened or RO water will be aggressive to pipework.
  • Comparing make-up water sources.

Common mistakes

  • Entering calcium as Ca instead of as CaCO₃ (multiply Ca by 2.5).
  • Using P alkalinity instead of total (M) alkalinity.
  • Using the basin temperature when scaling happens at the hot tube wall.

Assumptions and limits

  • 0–100 °C; the working form is approximate at high TDS (above about 10 000 mg/L), and a note appears there.
  • A note gives the common reading of the RSI bands.
  • An index of tendency only; inhibitors and flow decide what happens.

References

  • Langelier (1936)
  • J. AWWA 28
  • Ryznar (1944)
  • J. AWWA 36
  • Standard Methods 2330 (calcium carbonate saturation)

Questions and answers

What does a positive Langelier index mean?

The water is supersaturated with calcium carbonate and tends to deposit scale. Cooling water at 25 °C, pH 8.0, TDS 500, calcium 250 and alkalinity 100 mg/L has pHs 7.56 and LSI +0.44.

How is the Ryznar index read?

RSI = 2 pHs − pH. In common reading, below about 6 the water tends to scale, around 6 to 7 it is near balance, and above 7 it tends to be corrosive; the example gives RSI 7.1. The bands are a rule of practice, not exact limits.

Why does the index rise with temperature?

Calcium carbonate is less soluble in hot water, so pHs falls and the same water scales more on hot heat transfer surfaces than in the basin.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.