Worked example
Example: Feed TDS 100, silica 2, alkalinity 40 ppm; limits 3000 / 100 / 600. The inputs, in the units selected above:
| Input | Value |
|---|---|
| TDS | 100.00 ppm |
| Silica, as SiO₂ | 2.0000 ppm |
| Total alkalinity, as CaCO₃ | 40.000 ppm |
| TDS limit | 3,000.0 ppm |
| Silica limit | 100.00 ppm |
| Total alkalinity limit | 600.00 ppm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Blowdown needed, share of steam | 7.1429 % |
| Blowdown for TDS | 3.4483 % |
| Blowdown for silica | 2.0408 % |
| Blowdown for alkalinity | 7.1429 % |
| Cycles of concentration | 15.000 |
Open this example in the calculator and change any input.
Formula
\(b_i = \frac{f_i}{L_i - f_i} \quad (i = TDS,\ SiO_2,\ alk) \qquad b = \max_i b_i \qquad N = \frac{1 + b}{b}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f_{TDS}\), \(f_{SiO_2}\), \(f_{alk}\) | feedwater TDS, silica, alkalinity | – |
| \(L_{TDS}\), \(L_{SiO_2}\), \(L_{alk}\) | boiler water limits | – |
| \(b\) | blowdown needed, share of steam | – |
| \(b_{TDS}\) | blowdown for TDS | – |
| \(b_{SiO_2}\) | blowdown for silica | – |
| \(b_{alk}\) | blowdown for alkalinity | – |
| \(N\) | cycles of concentration | – |
Method and standards
Steady mass balance of a conserved solute in the drum: what enters with the feedwater leaves with the blowdown at the boiler water concentration (steam carries none).
Where it is used
- Setting continuous blowdown and TDS controllers.
- Choosing make-up treatment: which parameter is worth removing.
- Water and fuel budgets of the boiler house.
Common mistakes
- Controlling on TDS when silica or alkalinity is the real limit.
- Using limits for a lower pressure than the boiler runs at.
- Forgetting that alkalinity partly breaks down to CO₂, which leaves with the steam.
Assumptions and limits
- Steam carries no solids; parameters conserved in the drum; steady operation. At high pressure silica is carried by the steam; a note appears when silica governs.
- A feedwater value of zero leaves that parameter out of the comparison; when two give the same blowdown, both are named.
References
- Dissolved-solids mass balance of the boiler drum
Questions and answers
Which parameter sets the blowdown?
The one that reaches its limit first. With feedwater of 100 ppm TDS, 2 ppm silica and 40 ppm alkalinity, and limits of 3000, 100 and 600 ppm, alkalinity needs 7.1 % blowdown, more than TDS (3.4 %) or silica (2.0 %); the boiler runs at 15 cycles.
Where do the limits come from?
From your boiler maker or a water chemistry standard for the boiler pressure; they fall steeply as pressure rises. This calculator takes them as inputs.
How do I lower the blowdown?
Treat the limiting parameter in the make-up (dealkalisation for alkalinity, RO for silica and TDS) or return more condensate.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.