Worked example
Example: 10 ppb at 100 t/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Iron (or copper) in feedwater | 10.000 ppb |
| Feedwater flow | 100.00 t/h |
| Operating hours per year | 7,500.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Transport rate | 1.0000 g/h |
| Transported per year | 7.5000 kg |
Open this example in the calculator and change any input.
Formula
\(\dot m_{Fe} = c\,\dot m, \quad M_a = \dot m_{Fe} t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(c\) | Iron (or copper) in feedwater | - |
| \(\dot m\) | Feedwater flow | kg/s |
| \(t\) | Operating hours per year | s |
| \(\dot m_{Fe}\) | Transport rate | kg/s |
| \(M_a\) | Transported per year | kg |
Method and standards
Mass balance.
Where it is used
- Chemistry KPIs.
- Chemical cleaning planning.
Common mistakes
- ppm entered as ppb.
Assumptions and limits
- Average concentration. The result is the mass transported, not the mass deposited; operating hours are limited to one year (8784 h at most).
References
- Mass balance: rate = concentration × flow
Questions and answers
Why do a few ppb matter?
At 100 t/h, 10 ppb of iron carries about 7.5 kg a year into the boiler; most of it deposits on the tubes and part leaves with the blowdown.
Where does it come from?
Corrosion in feedwater heaters, condensate lines and the deaerator.
Cure?
Better pH control (amines), oxygen control and condensate polishing.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.