FireCADCalc

Chemical Dosing Pump: Solution Flow and Stroke Setting

Solution flow and stroke setting to dose a chemical at a concentration, from the solution strength and density and the pump's capacity.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolWater treatment plant

Inputs

Examples: 5 ppm at 50 t/hPhosphate 2 ppm

Results

Active chemical0.25000kg/h
Solution flow4.8544L/h
Stroke setting48.544%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5 ppm at 50 t/h. The inputs, in the units selected above:

InputValue
Water or feedwater flow50.000 t/h
Dose of active chemical5.0000 ppm
Active strength of the dosing solution5.0000 %
Solution density1,030.0 kg/m³
Pump capacity at 100 % stroke10.000 L/h

Applying the formula below gives:

ResultValue
Active chemical0.25000 kg/h
Solution flow4.8544 L/h
Stroke setting48.544 %

Open this example in the calculator and change any input.

Formula

\(\dot m_a = \dot m_w c, \quad \dot V_s = \frac{\dot m_a}{w\rho_s}, \quad s = \frac{\dot V_s}{\dot V_{max}}\)

Variables

Symbol Meaning SI unit
\(\dot m_w\) Water or feedwater flow kg/s
\(c\) Dose of active chemical -
\(w\) Active strength of the dosing solution -
\(\rho_s\) Solution density kg/m³
\(\dot V_{max}\) Pump capacity at 100 % stroke m³/s
\(\dot m_a\) Active chemical kg/s
\(\dot V_s\) Solution flow m³/s
\(s\) Stroke setting -

Method and standards

Mass balance.

Where it is used

  • Dosing system set-up.

Common mistakes

  • Dose of product used as active.

Assumptions and limits

  • Linear pump. A stroke above 100 % means the pump is too small; a note says so.

References

  • Mass balance: active chemical = flow × dose; solution = active/(strength × density)

Questions and answers

Why aim for mid-range stroke?

Metering pumps are least accurate near the ends of their range.

Strength or stroke?

Change the solution strength for large changes; fine-tune with stroke.

Dose as product or active?

This calculator works in active chemical; enter the product's active strength.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.