Worked example
Example: 1.5 t/h from 46 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Blowdown flow | 1,500.0 kg/h |
| Drum pressure (absolute) | 46.000 bar |
| Flash vessel pressure (absolute) | 1.0132 bar |
| Allowed discharge temperature | 60.000 °C |
| Cooling water temperature | 30.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flash steam | 471.83 kg/h |
| Residual water from the vessel | 1,028.2 kg/h |
| Quench (cooling) water | 1,375.7 kg/h |
| Total drain | 2,403.8 kg/h |
Open this example in the calculator and change any input.
Formula
\(x = \frac{h_f(p_d) - h_f(p_v)}{h_{fg}(p_v)}, \quad \dot m_c = \dot m_b(1 - x)\frac{h_f(p_v) - h(T_d)}{h(T_d) - h(T_c)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_b\) | Blowdown flow | kg/s |
| \(p_d\) | Drum pressure (absolute) | Pa |
| \(p_v\) | Flash vessel pressure (absolute) | Pa |
| \(T_d\) | Allowed discharge temperature | K |
| \(T_c\) | Cooling water temperature | K |
| \(\dot m_f\) | Flash steam | kg/s |
| \(\dot m_l\) | Residual water from the vessel | kg/s |
| \(\dot m_c\) | Quench (cooling) water | kg/s |
| \(\dot m_t\) | Total drain | kg/s |
Method and standards
Energy balance.
Where it is used
- Blowdown system design.
- Effluent compliance.
Common mistakes
- Ignoring the flash.
Assumptions and limits
- Adiabatic vessel; the flash steam leaves the vessel (vented or recovered). If it is condensed into the drain, the quench water needed is higher.
- The residual water is mixed with the cooling water at atmospheric pressure; with a pressurised flash vessel, any second flash when the water is let down to the drain is not modelled.
References
- Flash and mixing energy balances with IAPWS-IF97 enthalpies; the discharge limit is the user's consent value
Questions and answers
Why quench blowdown?
Drains and sewers have temperature limits; hot water also damages pipes and creates vapour.
How much flashes?
From a 46 bar(a) drum to atmosphere, about 30 % of the blowdown flashes.
Better option?
Recover flash steam to the deaerator and preheat make-up with the residual water.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.