Water Softener Sizing and Run Length

Resin volume and salt per regeneration for a water softener from flow, hardness, run time and resin capacity, and the run length of an installed resin volume.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserBoilerWater treatment plant

Inputs

Examples: 10 m³/h, 200 mg/L, 12 h run, capacity 50 g/L, salt 160 g/L30 m³/h, 350 mg/L, 8 h, 55 g/L, 200 g/L2 m³/h, 120 mg/L, 24 h, 45 g/L, 120 g/L

From the resin maker's curve at your salt dose and water quality.

Results

Resin volume needed480.00L
Salt per regeneration76.800kg
Hardness removed per run, as CaCO₃24.000kg
Run length of the installed resin12.500h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 m³/h, 200 mg/L, 12 h run, capacity 50 g/L, salt 160 g/L. The inputs, in the units selected above:

InputValue
Water flow10.000 m³/h
Total hardness of the raw water, as CaCO₃200.00 mg/L
Run time between regenerations12.000 h
Operating capacity of the resin, as CaCO₃50.000 g/L
Salt dose per litre of resin160.00 g/L
Installed resin volume (for its run length)0.50000 m³

Applying the formula below gives:

ResultValue
Resin volume needed480.00 L
Salt per regeneration76.800 kg
Hardness removed per run, as CaCO₃24.000 kg
Run length of the installed resin12.500 h

Open this example in the calculator and change any input.

Formula

\(L_h = \dot V\,t_r\,H \qquad V_r = \frac{L_h}{C_r} \qquad m_s = V_r\,s \qquad t_i = \frac{V_i\,C_r}{\dot V\,H}\)

Variables

Symbol Meaning SI unit
\(\dot V\) water flow m³/s
\(H\) total hardness as CaCO₃ kg/m³
\(t_r\) run time between regenerations s
\(C_r\) resin operating capacity as CaCO₃ kg/m³
\(s\) salt dose per volume of resin kg/m³
\(V_i\) installed resin volume m³
\(V_r\) resin volume needed m³
\(m_s\) salt per regeneration kg
\(L_h\) hardness removed per run kg
\(t_i\) run length of the installed resin s

Method and standards

Mass balance of an ion-exchange bed: the hardness load per run equals the resin volume times its operating capacity. Capacity and salt dose are the resin maker's data.

Where it is used

  • Sizing softeners for boiler make-up in process plants.
  • Checking regeneration frequency after a change in raw water.
  • Salt budgets.

Common mistakes

  • Using the total (theoretical) capacity instead of the operating capacity.
  • Forgetting the regeneration downtime when there is only one vessel.
  • Using hardness in mg/L as Ca, not as CaCO₃.

Assumptions and limits

  • Constant flow and hardness; no hardness leakage; capacity at your salt dose.
  • No design margin, minimum bed depth or regeneration downtime is included: add a margin on the resin, check the bed depth with the maker, and provide a second unit or storage for the regeneration time.

References

  • Ion-exchange mass balance (hardness load / operating capacity)

Questions and answers

How much resin does a softener need?

The hardness it removes per run divided by the resin's capacity. 10 m³/h of water at 200 mg/L hardness for 12 hours is 24 kg of hardness as CaCO₃; at 50 g/L capacity that is 480 L of resin and 77 kg of salt per regeneration at 160 g/L.

Where does the capacity come from?

The resin maker's curve: capacity rises with the salt dose but salt efficiency falls. 40–60 g/L as CaCO₃ is common for strong-acid cation resin; use the maker's figure for your salt dose.

How long will my existing softener run?

Enter the installed resin volume: 0.5 m³ at 50 g/L treating 10 m³/h of 200 mg/L water runs 12.5 hours.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.