Worked example
Example: 1.3 bar(a) DA, 2 ppm O2 in steam. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Deaerator pressure (absolute) | 1.3000 bar |
| Oxygen in the steam phase (by volume) | 2.0000 ppm |
| Target oxygen in the water (by mass) | 7.0000 ppb |
Applying the formula below gives:
| Result | Value |
|---|---|
| Saturation temperature | 107.11 °C |
| Distribution constant y/x | 52,412 |
| Equilibrium oxygen in the water (by mass) | 0.067778 ppb |
| Steam-phase oxygen for the target | 206.56 ppm |
Open this example in the calculator and change any input.
Formula
\(x = \frac{y}{K_D(T_{sat})}, \quad w = x\frac{M_{O_2}}{M_{H_2O}}, \quad y_{max} = K_D\,w_t\frac{M_{H_2O}}{M_{O_2}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Deaerator pressure (absolute) | Pa |
| \(y\) | Oxygen in the steam phase (by volume) | - |
| \(w_t\) | Target oxygen in the water (by mass) | - |
| \(T_{sat}\) | Saturation temperature | K |
| \(K_D\) | Distribution constant y/x | - |
| \(w\) | Equilibrium oxygen in the water (by mass) | - |
| \(y_{max}\) | Steam-phase oxygen for the target | - |
| \(x\) | Oxygen mole fraction in the water | - |
| \(M_{O_2}\) | Molar mass of oxygen | kg/kmol |
| \(M_{H_2O}\) | Molar mass of water | kg/kmol |
Method and standards
IAPWS G7-04.
Where it is used
- Deaerator performance checks.
- Vent rate studies.
Common mistakes
- Mass ppb treated as molar ppb.
Assumptions and limits
- Equilibrium at saturation.
- If the target would allow a steam phase of more than pure oxygen, y_max is not shown and a note says the target sets no limit.
References
- IAPWS G7-04
- Guideline on the Henry's Constant and Vapor-Liquid Distribution Constant for Gases in H₂O and D₂O at High Temperatures (2004); T_sat from IAPWS-IF97
Questions and answers
Why does a deaerator work?
At saturation oxygen strongly prefers the steam phase: K_D is in the tens of thousands near 100 °C.
Why vent?
Venting removes the oxygen-rich steam; without it oxygen builds up in the steam space and returns to the water.
Typical guarantee?
A commonly quoted figure for pressure deaerators is 0.005 cm³/L (about 7 ppb), which is the default target here; use the figure in your own purchase specification.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.