Worked example
Example: 10 t/h feed without deaerator, 7 ppm O2, sulphite, 20 ppm excess. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Feedwater flow | 10,000 kg/h |
| Dissolved oxygen in the feedwater | 7.0000 ppm |
| Scavenger | Sodium sulphite (Na₂SO₃) |
| Excess dose kept above the oxygen demand | 20.000 ppm |
| Active content of the product as dosed | 100.00 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Dose in the feedwater (active) | 75.145 ppm |
| Active chemical feed | 0.75145 kg/h |
| Product feed as supplied | 0.75145 kg/h |
| Stoichiometric ratio, kg chemical per kg O₂ | 7.8778 kg/kg |
Open this example in the calculator and change any input.
Formula
\(r_{sulphite} = \frac{2\,M_{Na_2SO_3}}{M_{O_2}} \qquad r_{hydrazine} = \frac{M_{N_2H_4}}{M_{O_2}}\)
\(D = O_2\,r + e \qquad \dot m_c = \dot m_{fw}\,D \qquad \dot m_p = \frac{\dot m_c}{w}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_{fw}\) | feedwater flow | kg/s |
| \(O_2\) | dissolved oxygen, mass fraction | – |
| \(\text{chem}\) | sodium sulphite or hydrazine | – |
| \(e\) | excess dose above the oxygen demand | – |
| \(w\) | active content of the product | – |
| \(D\) | dose in the feedwater | – |
| \(\dot m_c\) | active chemical feed | kg/s |
| \(\dot m_p\) | product feed | kg/s |
| \(r\) | stoichiometric ratio | kg/kg |
| \(M\) | molar masses from IUPAC atomic weights | kg/kmol |
Method and standards
Stoichiometry of the scavenging reactions with molar masses from IUPAC 2013 atomic weights.
Where it is used
- Dosing pumps and chemical budgets for boilers.
- Comparing chemical scavenging with feed tank heating or a deaerator.
- Checking a supplier's recommended dose.
Common mistakes
- Dosing several ppm of oxygen chemically instead of deaerating first.
- Using the product rate as active chemical (solutions are often 10–40 %).
- Overdosing sulphite in high-pressure boilers, where it decomposes.
Assumptions and limits
- Complete reaction; oxygen measured where the dose is injected.
- The excess is a feedwater concentration. The boiler-water residual that programmes control depends on the cycles of concentration and blowdown, which are not modelled here.
- Sulphite decomposes in high-pressure boilers; there is no pressure input, so the page always reminds you of this for sulphite.
References
- Reaction stoichiometry (2 Na2SO3 + O2 → 2 Na2SO4; N2H4 + O2 → N2 + 2 H2O)
- IUPAC 2013 atomic weights
Questions and answers
How much sodium sulphite removes 1 ppm of oxygen?
7.88 ppm of pure sodium sulphite by the reaction 2 Na₂SO₃ + O₂ → 2 Na₂SO₄. A 10 t/h boiler without a deaerator, with 7 ppm oxygen and a 20 ppm excess, needs 75 ppm, about 0.75 kg/h.
And hydrazine?
About 1 ppm per ppm of oxygen (N₂H₄ + O₂ → N₂ + 2 H₂O). It adds no solids, so high-pressure boilers use it or its safer replacements; it is toxic and handled under strict rules.
Why the excess?
The reaction must finish in the feed line and the boiler; programmes keep a residual of sulphite in the boiler water. Your water-treatment supplier sets it.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.