Worked example
Example: 10 t/h, 10.5 bar(a), blowdown 8 % to 4 %, coal. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam generated | 10,000 kg/h |
| Blowdown now, as a share of steam | 8.0000 % |
| Blowdown after, as a share of steam | 4.0000 % |
| Drum pressure (absolute) | 10.500 bar |
| Feedwater temperature | 105.00 °C |
| Boiler efficiency (on GCV) | 78.000 % |
| Gross calorific value of the fuel, as fired | 18,600 kJ/kg |
| Operating hours per year | 8,000.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Fuel saved | 9.1316 kg/h |
| Fuel saved per year | 73.053 t |
| Treated water saved per year | 3,200.0 t |
| Heat no longer blown down | 36.801 kW |
| Heat per kg of blowdown above feedwater | 331.20 kJ/kg |
Open this example in the calculator and change any input.
Formula
\(\Delta\dot Q = S\,(b_1 - b_2)\,(h_f - h_{fw}) \qquad \Delta\dot m_f = \frac{\Delta\dot Q}{\eta_1\,GCV}\)
\(\Delta m_f = \Delta\dot m_f\,t_{op} \qquad \Delta m_w = S\,(b_1 - b_2)\,t_{op}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | steam generated | kg/s |
| \(b_1\) | blowdown now, share of steam | – |
| \(b_2\) | blowdown after, share of steam | – |
| \(p\) | drum pressure, absolute | Pa |
| \(T_{fw}\) | feedwater temperature | K |
| \(\eta_1\) | boiler efficiency on GCV | – |
| \(GCV\) | gross calorific value | J/kg |
| \(t_{op}\) | operating hours per year | s |
| \(\Delta\dot m_f\) | fuel saved | kg/s |
| \(\Delta m_f\) | fuel saved per year | kg |
| \(\Delta m_w\) | water saved per year | kg |
| \(\Delta\dot Q\) | heat no longer blown down | W |
| \(h_f - h_{fw}\) | heat per kg of blowdown above feedwater | J/kg |
| \(h_f\) | saturated water enthalpy at drum pressure | J/kg |
| \(h_{fw}\) | feedwater enthalpy | J/kg |
Method and standards
Blowdown leaves the drum as saturated water; each kg was heated from the feedwater temperature. Enthalpies by FireCAD's IAPWS-IF97; fuel from the boiler efficiency on GCV.
Where it is used
- Justifying automatic TDS (conductivity) blowdown control.
- Valuing better make-up treatment or more condensate return.
- Water audits: blowdown is often the largest controllable water loss of a boiler house.
Common mistakes
- Expressing blowdown as a share of feedwater in one place and of steam in another.
- Lowering blowdown below what the water chemistry needs, causing carry-over or deposits.
- Ignoring heat already recovered from blowdown.
Assumptions and limits
- No blowdown heat recovery; same steam output and efficiency.
- Water saved counted as treated make-up water; the treatment chemicals saved are in proportion but not calculated.
- Blowdown is a share of steam. If yours is quoted as a share of feedwater \(b_{fw}\), convert with \(b = b_{fw} / (1 - b_{fw})\).
- With existing blowdown heat recovery the saving is smaller than shown; a note on the result says so.
References
- IAPWS R7-97(2012) IF97
- first law heat balance
Questions and answers
How much does reducing blowdown save?
A 10 t/h boiler at 10.5 bar(a) cutting blowdown from 8 to 4 % of steam stops 400 kg/h of water at 182 °C leaving the drum: 36.8 kW of heat, 9.1 kg/h of coal at 78 % efficiency and 18.6 MJ/kg, 73 t of coal and 3200 t of treated water in 8000 hours.
How do I lower blowdown safely?
Improve the make-up treatment (softener, RO, dealkaliser), return more condensate, and control blowdown by conductivity (TDS) instead of a fixed valve opening. Keep the boiler water within the limits of the boiler maker or the water chemistry standard.
What if blowdown heat is already recovered?
Then the saving is smaller: a flash vessel and heat exchanger already recover much of the heat. This calculator gives the gross saving with no recovery.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.