Worked example
Example: Ganapathy: 500 BHP, 125 psig, 230 °F feed, 5 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Boiler horsepower | 500.00 - |
| Saturated steam pressure (absolute) | 9.6320 bar |
| Feedwater temperature | 110.00 °C |
| Blowdown as a share of steam | 5.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heat output | 4,905.3 kW |
| Steam generated | 7,582.1 kg/h |
| Blowdown | 379.11 kg/h |
Open this example in the calculator and change any input.
Formula
\(W = \frac{BHP \times 33\,475\ \mathrm{Btu/h}}{(h_g - h_{fw}) + BD\,(h_f - h_{fw})}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(BHP\) | Boiler horsepower | - |
| \(p\) | Saturated steam pressure (absolute) | Pa |
| \(T_{fw}\) | Feedwater temperature | K |
| \(BD\) | Blowdown as a share of steam | - |
| \(Q\) | Heat output | W |
| \(W\) | Steam generated | kg/s |
| \(W_{BD}\) | Blowdown | kg/s |
| \(h_g, h_f, h_{fw}\) | Enthalpies of saturated steam, saturated water and feedwater | J/kg |
Method and standards
Ganapathy's energy balance with IF97 enthalpies.
Where it is used
- Rating package fire-tube boilers.
- Comparing US and metric boiler data.
Common mistakes
- Using kg/h 'from and at' as actual steam.
- Ignoring blowdown.
Assumptions and limits
- Saturated steam; heat losses within the rating.
- Feedwater enthalpy is taken as saturated liquid at the feedwater temperature, not compressed liquid at boiler pressure; the difference is well under 0.5 % at shell-boiler pressures.
References
- Ganapathy
- Steam Plant Calculations Manual
- 2nd ed. (Marcel Dekker, 1993)
- Q1.08 (steam output of a boiler from its horsepower)
- Steam and water enthalpies from IAPWS-IF97
Questions and answers
What is a boiler horsepower?
33,475 Btu/h, the heat to evaporate 34.5 lb/h of water from and at 212 °F.
Why does blowdown reduce the steam?
Blowdown leaves as hot saturated water that was heated but not evaporated.
Is the 500 BHP example in Ganapathy?
Yes: 500 BHP at 125 psig, 230 °F feed and 5 % blowdown gives about 16,700 lb/h.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.