Worked example
Example: Set 10.5 bar g, 4 % blowdown, working 9.5 bar g. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Set pressure | 10.500 bar g |
| Blowdown, share of set pressure | 4.0000 % |
| Normal working pressure | 9.5000 bar g |
Applying the formula below gives:
| Result | Value |
|---|---|
| Reseat pressure | 10.080 bar g |
| Reseat pressure minus working pressure | 58.000 kPa |
| Working pressure as a share of set pressure (gauge) | 90.476 % |
Open this example in the calculator and change any input.
Formula
\(p_r = p_s\,(1 - b) \qquad \Delta p = p_r - p_w \qquad \frac{p_w}{p_s} \quad \text{(gauge pressures)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p_s\) | set pressure (gauge) | Pa |
| \(b\) | blowdown, share of set pressure | – |
| \(p_w\) | normal working pressure (gauge) | Pa |
| \(p_r\) | reseat pressure (gauge) | Pa |
| \(\Delta p\) | reseat minus working pressure | Pa |
| \(p_w/p_s\) | working pressure as a share of set pressure | – |
Method and standards
Blowdown is the difference between set and reseat pressure as a share of set pressure, on gauge pressure. The calculator does not size the valve; that is a code calculation.
Where it is used
- Setting safety valves after overhaul.
- Choosing the working pressure margin of a boiler.
- Investigating simmering or leaking valves.
Common mistakes
- Mixing gauge and absolute pressures.
- Running the boiler so close to set pressure that the valve never reseats.
- Changing the blowdown ring without the maker's procedure.
Assumptions and limits
- Blowdown as stated by the valve maker; no accumulation or backpressure effects.
References
- Definition of blowdown as a share of set pressure (gauge)
Questions and answers
How do I find a safety valve's reseat pressure?
Set pressure less the blowdown. A valve set at 10.5 bar g with 4 % blowdown reseats at 10.08 bar g; with the boiler working at 9.5 bar g it closes with 0.58 bar to spare.
Why must the working pressure stay below the reseat pressure?
If the boiler runs above the reseat pressure, a valve that lifts will not close again until the pressure falls, wasting steam and wearing the seat; close to it the valve simmers and leaks.
What blowdown should the valve have?
The valve maker sets it with the adjusting ring, within the limits of the boiler code you follow. This page takes it as an input.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.