Worked example
Example: Bagasse 70 % on GCV. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Efficiency on GCV | 70.000 % |
| Fuel gross calorific value | 9,600.0 kJ/kg |
| Fuel net calorific value | 7,400.0 kJ/kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Efficiency on NCV | 90.811 % |
| Difference (net − gross) | 20.811 % |
Open this example in the calculator and change any input.
Formula
\(\eta_{NCV} = \eta_{GCV} \frac{GCV}{NCV}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\eta_{GCV}\) | Efficiency on GCV | - |
| \(GCV\) | Fuel gross calorific value | J/kg |
| \(NCV\) | Fuel net calorific value | J/kg |
| \(\eta_{NCV}\) | Efficiency on NCV | - |
| \(\Delta\eta\) | Difference (net − gross) | - |
Method and standards
Definitions.
Where it is used
- Comparing quotations.
- Reports to different standards.
Common mistakes
- Comparing gross with net.
Assumptions and limits
- Same fuel, with GCV and NCV on the same basis (as fired). The NCV of a wet fuel depends strongly on its moisture, so both values must be for the fuel as it is fired.
- For the reverse conversion use \(\eta_{GCV} = \eta_{NCV}\,NCV/GCV\).
References
- Same useful heat on two bases: η_NCV = η_GCV × GCV/NCV
Questions and answers
Why do bagasse boilers quote higher net efficiencies?
Wet bagasse has a large gap between GCV and NCV.
Which basis for guarantees?
State it: India and the US mostly use GCV, Europe NCV.
Comparing two boilers?
Only on the same basis and the same fuel.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.