Worked example
Example: Day: 200 t steam, 10 t/h MCR, ran 22 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam generated in the period | 200.00 t |
| Length of the period | 24.000 h |
| Rated capacity (MCR) | 10,000 kg/h |
| Running hours in the period | 22.000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Load factor (average load while running ÷ MCR) | 90.909 % |
| Capacity utilisation over the whole period | 83.333 % |
| Running share of the period | 91.667 % |
| Average steam flow while running | 9,090.9 kg/h |
Open this example in the calculator and change any input.
Formula
\(\bar{\dot m} = \frac{S}{t_r} \qquad LF = \frac{\bar{\dot m}}{\dot m_{MCR}} \qquad CUF = \frac{S}{\dot m_{MCR}\,t_p} \qquad A = \frac{t_r}{t_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | steam generated in the period | kg |
| \(t_p\) | length of the period | s |
| \(\dot m_{MCR}\) | rated capacity (maximum continuous rating) | kg/s |
| \(t_r\) | running hours | s |
| \(LF\) | load factor | – |
| \(CUF\) | capacity utilisation | – |
| \(A\) | running share of the period | – |
| \(\bar{\dot m}\) | average steam flow while running | kg/s |
Method and standards
Standard plant performance definitions; note that \(CUF = LF \cdot A\).
Where it is used
- Daily and monthly boiler house reports.
- Deciding whether a standby boiler or a smaller boiler would serve the load better.
- Comparing boilers and sites.
Common mistakes
- Dividing by calendar hours and calling it load factor.
- Using a steam meter total that includes another boiler's steam.
- Using the nameplate rating when the boiler is derated.
Assumptions and limits
- Steam totals and hours from the same period; the rating is the current MCR.
- \(A\) is the share of the period the boiler ran, not its availability: a boiler that was available but held on standby counts as not running.
References
- Plant performance definitions (load factor, capacity utilisation, running share)
Questions and answers
How is boiler load factor calculated?
Average load while running divided by the rated capacity. A 10 t/h boiler that made 200 t of steam in 22 running hours averaged 9.09 t/h: a load factor of 90.9 %. Over the whole 24-hour day its capacity utilisation was 83.3 % and it ran 91.7 % of the time.
Load factor or capacity utilisation?
Load factor shows how hard the boiler works when it runs; capacity utilisation also counts the time it stood idle. A low utilisation with a high load factor means too much downtime; the reverse means the boiler is oversized for the load.
Why does it matter?
Efficiency falls at low load, and fixed costs are spread over less steam. Daily and monthly load factors are part of most boiler house reports.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.