Worked example
Example: Bagasse boiler. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Steam flow (meter) | 60.000 t/h |
| Feedwater flow (meter) | 62.500 t/h |
| Blowdown | 1.5000 t/h |
| Fuel flow | 27.000 t/h |
| Fuel GCV | 9,600.0 kJ/kg |
| Boiler efficiency (GCV) | 70.000 % |
| Steam pressure (absolute) | 46.000 bar |
| Steam temperature | 440.00 °C |
| Feedwater temperature | 105.00 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Steam from feedwater − blowdown | 61.000 t/h |
| Steam from fuel heat × efficiency | 63.178 t/h |
| Steam meter vs water balance | -1.6393 % |
| Steam meter vs fuel balance | -5.0301 % |
Open this example in the calculator and change any input.
Formula
\(\dot m_{s,1} = \dot m_{fw} - \dot m_{bd}, \quad \dot m_{s,2} = \frac{\dot m_{fuel}GCV\,\eta - \dot m_{bd}(h_f - h_{fw})}{h_s - h_{fw}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_s\) | Steam flow (meter) | kg/s |
| \(\dot m_{fw}\) | Feedwater flow (meter) | kg/s |
| \(\dot m_{bd}\) | Blowdown | kg/s |
| \(\dot m_{fuel}\) | Fuel flow | kg/s |
| \(GCV\) | Fuel GCV | J/kg |
| \(\eta\) | Boiler efficiency (GCV) | - |
| \(p\) | Steam pressure (absolute) | Pa |
| \(T_s\) | Steam temperature | K |
| \(T_{fw}\) | Feedwater temperature | K |
| \(\dot m_{s,1}\) | Steam from feedwater − blowdown | kg/s |
| \(\dot m_{s,2}\) | Steam from fuel heat × efficiency | kg/s |
| \(\epsilon_1\) | Steam meter vs water balance | - |
| \(\epsilon_2\) | Steam meter vs fuel balance | - |
Method and standards
Mass balance (steam = feedwater − blowdown) and energy balance (fuel heat × efficiency, less the heat to the blowdown as saturated water, over the heat per kg of steam), with IAPWS-IF97 enthalpies.
Where it is used
- Meter health checks.
- Efficiency test preparation.
Common mistakes
- Uncompensated steam meter.
Assumptions and limits
- Steady load.
- Attemperator spray taken from the feedwater after its meter, vents, drains and soot-blowing steam taken before the steam meter are not in the balance; allow for them when comparing.
- Feedwater liquid at the steam pressure; feedwater flow above the blowdown; fuel flow above zero.
References
- Mass balance and energy balance with IAPWS-IF97 enthalpies
Questions and answers
Why two balances?
The water balance checks the flow meters; the heat balance checks them against fuel and efficiency.
Typical disagreement?
A few per cent is normal; larger and steady errors point to a meter.
Efficiency unknown?
Use the indirect (loss) method value; then the heat balance checks the direct efficiency.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.