Worked example
Example: 3000 m³/h, 10 to 30 °C, 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow (at the inlet) | 3,000.0 m³/h |
| Inlet air temperature | 10.000 °C |
| Inlet relative humidity | 50.000 % |
| Outlet air temperature | 30.000 °C |
| Supply voltage (line) | 415.00 V |
| Supply | Three-phase |
| Barometric pressure (absolute) | 101.33 kPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Heater power | 20.922 kW |
| Line current | 29.106 A |
| Outlet relative humidity | 14.460 % |
Open this example in the calculator and change any input.
Formula
\(P = \dot m_{da}\left[h(T_2, W) - h(T_1, W)\right], \quad I = \frac{P}{\sqrt{3}U}\ \text{(three-phase)},\quad I = \frac{P}{U}\ \text{(single-phase)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow (at the inlet) | m³/s |
| \(T_1\) | Inlet air temperature | K |
| \(\varphi_1\) | Inlet relative humidity | - |
| \(T_2\) | Outlet air temperature | K |
| \(U\) | Supply voltage (line) | V |
| \(\text{phases}\) | Supply | - |
| \(p\) | Barometric pressure (absolute) | Pa |
| \(P\) | Heater power | W |
| \(I\) | Line current | A |
| \(\varphi_2\) | Outlet relative humidity | - |
Method and standards
Energy balance.
Where it is used
- Reheat and frost heaters.
- Panel and control room heaters.
Common mistakes
- Volume at the outlet.
- Forgetting the √3.
Assumptions and limits
- Resistive heater, unity power factor.
References
- Moist-air energy balance (ASHRAE Handbook—Fundamentals ch. 1); P = √3 U I for three-phase
Questions and answers
3000 m³/h from 10 to 30 °C?
About 20.9 kW, 29 A on 415 V three-phase.
Why does RH fall?
Heating adds no moisture, so relative humidity drops.
Safety?
Interlock with air flow and fit a high-limit cut-out.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.