Heating Coil Load and Hot Water Flow

Load of an air heating coil from air flow and temperatures (moist-air enthalpy), and the hot water flow for its supply and return temperatures (IF97).

IAPWS-IF97 (water and steam)

Inputs

Examples: 10 000 m³/h, 5 to 28 °C, 80/60 °C waterReheat 5000 m³/h, 12 to 22 °C, 70/50 °C

Results

Water enthalpies at 10 bar(a) (IAPWS-IF97). For steam coils divide the load by the latent heat instead.

Coil load81.651kW
Hot water flow3.5107t/h
Leaving relative humidity18.453%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 000 m³/h, 5 to 28 °C, 80/60 °C water. The inputs, in the units selected above:

InputValue
Air flow (at the inlet)10,000 m³/h
Air in5.0000 °C
Inlet relative humidity80.000 %
Air out28.000 °C
Hot water in80.000 °C
Hot water out60.000 °C
Barometric pressure (absolute)101.33 kPa

Applying the formula below gives:

ResultValue
Coil load81.651 kW
Hot water flow3.5107 t/h
Leaving relative humidity18.453 %

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_{da}\left[h(T_2, W) - h(T_1, W)\right], \quad \dot m_w = \frac{\dot Q}{h_{w1} - h_{w2}}\)

Variables

Symbol Meaning SI unit
\(\dot V\) Air flow (at the inlet) m³/s
\(T_1\) Air in K
\(\varphi_1\) Inlet relative humidity -
\(T_2\) Air out K
\(T_{w1}\) Hot water in K
\(T_{w2}\) Hot water out K
\(p\) Barometric pressure (absolute) Pa
\(\dot Q\) Coil load W
\(\dot m_w\) Hot water flow kg/s
\(\varphi_2\) Leaving relative humidity -

Method and standards

Energy balance.

Where it is used

  • AHU and fresh-air unit heating coils.
  • Hot water pump sizing.

Common mistakes

  • Volume at the outlet.
  • Water ΔT too large for the coil.

Assumptions and limits

  • Steady state. Hot water up to 179.9 °C (liquid at the 10 bar(a) used for its properties).

References

  • Moist-air energy balance (ASHRAE Handbook—Fundamentals ch. 1); water enthalpies from IAPWS-IF97

Questions and answers

10,000 m³/h from 5 to 28 °C with 80/60 °C water?

About 82 kW and 3.5 t/h of hot water.

Frost?

Coils with outdoor air below 0 °C need frost protection.

Steam coil?

Steam flow = load / latent heat at the coil pressure.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.