Worked example
Example: 18 000 m³/h, 2.5 m/s, chosen 2.4 m wide. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Air flow | 18,000 m³/h |
| Design face velocity | 2.5000 m/s |
| Coil height | 900.00 mm |
| Chosen width (0 to use the width found) | 2,400.0 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Face area needed | 2.0000 m² |
| Width needed for the height | 2,222.2 mm |
| Face velocity with the chosen size | 2.3148 m/s |
Open this example in the calculator and change any input.
Formula
\(A = \frac{\dot V}{v_f}, \quad W = \frac{A}{H}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Air flow | m³/s |
| \(v_f\) | Design face velocity | m/s |
| \(H\) | Coil height | m |
| \(W_c\) | Chosen width (0 to use the width found) | m |
| \(A\) | Face area needed | m² |
| \(W\) | Width needed for the height | m |
| \(v_a\) | Face velocity with the chosen size | m/s |
Method and standards
Continuity.
Where it is used
- AHU and fan coil selection.
- Checking existing coils.
Common mistakes
- Gross casing area instead of finned area.
- Ignoring condensate carry-over.
Assumptions and limits
- Uniform face velocity.
References
- Continuity A = V̇ / v
Questions and answers
18,000 m³/h at 2.5 m/s?
2.0 m² of face: 2.22 m wide at 0.9 m high.
Why limit velocity on cooling coils?
High velocity lifts condensate off the fins into the duct.
Heating coils?
Can run faster, often 3–4 m/s.