Worked example
Example: Two 600 × 300 grilles. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Total air flow | 4,000.0 m³/h |
| Grille width | 600.00 mm |
| Grille height | 300.00 mm |
| Free-area ratio | 70.000 % |
| Number of grilles | 2.0000 - |
| Target face velocity (on the gross W × H, not the core) | 2.0000 m/s |
Applying the formula below gives:
| Result | Value |
|---|---|
| Face velocity | 3.0864 m/s |
| Free-area (core) velocity | 4.4092 m/s |
| Grilles needed for the target (rounded up) | 4.0000 |
Open this example in the calculator and change any input.
Formula
\(v_f = \frac{\dot V}{n W H}, \quad v_c = \frac{v_f}{f}, \quad n_t = \left\lceil\frac{\dot V}{W H v_t}\right\rceil\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Total air flow | m³/s |
| \(W\) | Grille width | m |
| \(H\) | Grille height | m |
| \(f\) | Free-area ratio | - |
| \(n\) | Number of grilles | - |
| \(v_t\) | Target face velocity (on the gross W × H, not the core) | m/s |
| \(v_f\) | Face velocity | m/s |
| \(v_c\) | Free-area (core) velocity | m/s |
| \(n_t\) | Grilles needed for the target (rounded up) | - |
Method and standards
Continuity.
Where it is used
- Supply and return grille selection.
- Louvres for plant rooms.
Common mistakes
- Gross area for core velocity.
- One grille's flow as the total.
Assumptions and limits
- Uniform flow. The target is a face velocity on the gross grille area W × H; the core velocity on the free area is higher by 1/f.
References
- Continuity v = V̇/A; core velocity on the free area
Questions and answers
4000 m³/h through two 600 × 300 grilles?
About 3.1 m/s face, 4.4 m/s through the free area.
Why keep it low?
Noise and draughts rise quickly with velocity.
Louvres on outside walls?
Keep the free-area velocity low enough to stop rain being drawn in.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.