FireCADCalc

Duct Sheet Metal Area, Weight and Insulation Quantity

Sheet metal area and weight of rectangular or round ductwork from size, length and thickness, with the external insulation area and volume, for estimating.

Inputs

Examples: Rectangular 800 × 500, 50 m, 25 mm insulationRound 400 mm, 30 m, bare

Results

Sheet area (with allowance)149.50m²
Sheet weight938.86kg
Insulation outer area140.00m²
Insulation volume3.3750m³

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Rectangular 800 × 500, 50 m, 25 mm insulation. The inputs, in the units selected above:

InputValue
Duct shapeRectangular
Diameter (round)400.00 mm
Width (rectangular)800.00 mm
Height (rectangular)500.00 mm
Length50.000 m
Sheet thickness0.80000 mm
Sheet density7,850.0 kg/m³
Allowance for seams, joints and stiffeners15.000 %
Insulation thickness (0 if none)25.000 mm

Applying the formula below gives:

ResultValue
Sheet area (with allowance)149.50 m²
Sheet weight938.86 kg
Insulation outer area140.00 m²
Insulation volume3.3750 m³

Open this example in the calculator and change any input.

Formula

\(A_s = P L (1 + k_s), \quad m = A_s t \rho\) \(A_i = P_i L, \quad V_i = (A_{out} - A_{in}) L, \quad P_i = \pi(D + 2t_i)\ \text{or}\ 2(W + H + 4t_i), \quad A_{out} = \frac{\pi (D + 2t_i)^2}{4}\ \text{or}\ (W + 2t_i)(H + 2t_i)\)

Variables

Symbol Meaning SI unit
\(\text{shape}\) Duct shape -
\(D\) Diameter (round) m
\(W\) Width (rectangular) m
\(H\) Height (rectangular) m
\(L\) Length m
\(t\) Sheet thickness m
\(\rho\) Sheet density kg/m³
\(k_s\) Allowance for seams, joints and stiffeners -
\(t_i\) Insulation thickness (0 if none) m
\(A_s\) Sheet area (with allowance) m²
\(m\) Sheet weight kg
\(A_i\) Insulation outer area m²
\(V_i\) Insulation volume m³

Method and standards

Geometry.

Where it is used

  • Ductwork estimates and bills of quantities.
  • Insulation orders.

Common mistakes

  • Ignoring seams and stiffeners.
  • Outer perimeter for sheet area.

Assumptions and limits

  • Straight duct.
  • Rectangular insulation is taken with square outer corners, slightly overstating its area and volume.

References

  • Perimeter × length with allowance (estimating practice)

Questions and answers

50 m of 800 × 500 duct in 0.8 mm GI with 15 % allowance?

About 150 m² of sheet, roughly 940 kg.

Which thickness?

Your duct standard sets it by size and pressure class.

Fittings?

Measure them along their centre line or add a share.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.