VAV Fan Power and Energy at Part Flow

Fan pressure and power of a variable-air-volume system at part flow with a duct static-pressure set point, compared with the cube law and constant-volume operation.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 10 m³/s, 1,000 Pa, 250 Pa set point, 60 % flowStatic reset to 100 Pa, 50 % flow

Results

System curve Δp = Δp_sp + (Δp_d − Δp_sp)r² with speed control; efficiency held constant (drive and motor losses rise at low load). Resetting the static set point lowers the fixed part and saves more.

Fan pressure at part flow520.00Pa
Fan power at part flow4.8000kW
Fan power at design15.385kW
Power ratio31.200%
Cube-law ratio21.600%
Energy saved against constant volume42,338kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 10 m³/s, 1,000 Pa, 250 Pa set point, 60 % flow. The inputs, in the units selected above:

InputValue
Design air flow36,000 m³/h
Design fan pressure1,000.0 Pa
Static pressure set point (fixed part)250.00 Pa
Overall fan efficiency65.000 %
Flow fraction60.000 %
Hours at this flow per year4,000.0 h

Applying the formula below gives:

ResultValue
Fan pressure at part flow520.00 Pa
Fan power at part flow4.8000 kW
Fan power at design15.385 kW
Power ratio31.200 %
Cube-law ratio21.600 %
Energy saved against constant volume42,338 kWh

Open this example in the calculator and change any input.

Formula

\(\Delta p = \Delta p_{sp} + (\Delta p_d - \Delta p_{sp})r^2, \quad W = \frac{r\dot V_d\Delta p}{\eta}\)

Variables

Symbol Meaning SI unit
\(\dot V_d\) Design air flow m³/s
\(\Delta p_d\) Design fan pressure Pa
\(\Delta p_{sp}\) Static pressure set point (fixed part) Pa
\(\eta\) Overall fan efficiency -
\(r\) Flow fraction -
\(t\) Hours at this flow per year s
\(\Delta p\) Fan pressure at part flow Pa
\(W\) Fan power at part flow W
\(W_d\) Fan power at design W
\(W/W_d\) Power ratio -
\(r^3\) Cube-law ratio -
\(\Delta E\) Energy saved against constant volume J

Method and standards

Fan and system curves.

Where it is used

  • VAV retrofit savings.
  • Comparing control strategies.

Common mistakes

  • Assuming the cube law with a fixed set point.
  • Ignoring drive losses at low speed.

Assumptions and limits

  • Fan efficiency is held at its design value at part flow. In practice fan, motor and drive efficiencies fall at low load, so the part-flow power is higher and the saving smaller than shown.

  • Constant efficiency; quadratic system curve above the set point.

References

  • ASHRAE Handbook—Fundamentals (2017)
  • ch. 21 and ASHRAE Handbook—HVAC Applications (2019)
  • ch. 42 (fan–system interaction with a fixed static set point)

Questions and answers

Why not the full cube-law saving?

The duct static set point keeps part of the pressure constant, so power falls more slowly than flow cubed.

What is static pressure reset?

Lowering the set point until the most open VAV box is nearly fully open; it recovers much of the lost saving.

What do the defaults represent?

A 10 m³/s air handler at 1,000 Pa with a 250 Pa set point running at 60 % flow.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.