Worked example
Example: Test at 500 Pa, run at 300 Pa. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Leakage measured at the test pressure | 50.000 L/s |
| Test pressure | 50.986 mmWC |
| Average operating pressure | 30.591 mmWC |
| Flow exponent | 0.65000 - |
| System air flow | 9,000.0 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Leakage at operating pressure | 35.873 L/s |
| Share of system air flow | 1.4349 % |
Open this example in the calculator and change any input.
Formula
\(\dot V_2 = \dot V_1\left(\frac{\Delta p_2}{\Delta p_1}\right)^n, \quad x = \frac{\dot V_2}{\dot V_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_1\) | Leakage measured at the test pressure | m³/s |
| \(\Delta p_1\) | Test pressure | Pa |
| \(\Delta p_2\) | Average operating pressure | Pa |
| \(n\) | Flow exponent | - |
| \(\dot V_s\) | System air flow | m³/s |
| \(\dot V_2\) | Leakage at operating pressure | m³/s |
| \(x\) | Share of system air flow | - |
Method and standards
Power law.
Where it is used
- Duct testing and commissioning.
- Fan sizing allowances.
Common mistakes
- Linear scaling with pressure.
- Peak instead of average duct pressure.
Assumptions and limits
- Same leak paths at both pressures.
- The share is not shown when the system air flow is zero.
References
- Power-law leakage Q = C Δpⁿ with n = 0.65 for ducts (ASHRAE Handbook—Fundamentals (2017), ch. 21, duct leakage)
Questions and answers
50 L/s at 500 Pa test, 300 Pa operating?
About 36 L/s, 1.4 % of 2.5 m³/s.
Why 0.65?
Real leaks lie between orifice and crack flow.
Acceptable leakage?
Your specification's class sets it.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.