FireCADCalc

Duct Size from Flow and Velocity

Round diameter and rectangular width and height of an air or flue gas duct for a volume flow, design velocity and aspect ratio, with the equivalent diameter.

Thermic fluid heatingFan and blower

Inputs

Examples: Air 20 m³/s at 15 m/s, aspect 1.6Flue gas 45 m³/s at 18 m/s, squareAir 2 m³/s at 10 m/s, aspect 2

From your specification or duct design standard; the calculator does not suggest one.

Results

Round duct inside diameter1,302.9mm
Rectangular duct width1,460.6mm
Rectangular duct height912.87mm
Flow area1.3333m²
Equivalent diameter of the rectangle (Huebscher)1,253.7mm

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Air 20 m³/s at 15 m/s, aspect 1.6. The inputs, in the units selected above:

InputValue
Volume flow (actual)72,000 m³/h
Design velocity15.000 m/s
Aspect ratio of the rectangular duct (width / height)1.6000 -

Applying the formula below gives:

ResultValue
Round duct inside diameter1,302.9 mm
Rectangular duct width1,460.6 mm
Rectangular duct height912.87 mm
Flow area1.3333 m²
Equivalent diameter of the rectangle (Huebscher)1,253.7 mm

Open this example in the calculator and change any input.

Formula

\(A = \frac{\dot V}{v} \qquad D = \sqrt{\frac{4A}{\pi}} \qquad a = \sqrt{A \cdot AR} \qquad b = \frac{a}{AR} \qquad D_e = \frac{1.30\,(ab)^{0.625}}{(a+b)^{0.25}}\)

Variables

Symbol Meaning SI unit
\(\dot V\) actual volume flow m³/s
\(v\) design velocity m/s
\(AR\) aspect ratio width / height –
\(D\) round duct inside diameter m
\(a\) rectangular duct width m
\(b\) rectangular duct height m
\(A\) flow area m²
\(D_e\) equivalent diameter of the rectangle m

Method and standards

Continuity for the flow area; Huebscher's equivalent diameter (ASHRAE Handbook—Fundamentals, Duct Design).

Where it is used

  • First sizing of air and flue gas ducts.
  • Checking duct velocities for erosion and noise.
  • Layout studies.

Common mistakes

  • Using normal volume flow instead of actual.
  • Choosing high velocities in dusty gas, which erodes ducts.
  • Ignoring pressure drop on long runs.

Assumptions and limits

  • Inside dimensions; add insulation, lining or refractory thickness for the outside size.
  • Round the result to the standard sizes you use and recheck the velocity.
  • The rectangle has the same area (same velocity) as the round duct, so its friction-equivalent diameter D_e is smaller than D and it has more friction per metre. For a rectangle equal in friction, use the equal-friction sizing calculator.

References

  • Continuity equation; Huebscher (1948) equivalent diameter

Questions and answers

How do I size a duct?

Area = flow ÷ velocity. 20 m³/s at 15 m/s needs 1.33 m²: a 1 303 mm round duct, or 1 461 × 913 mm rectangular at an aspect ratio of 1.6.

Which velocity should I use?

The one in your specification or duct design standard; it balances duct cost against pressure drop, noise and erosion. The calculator does not suggest one.

Why is the equivalent diameter smaller than the round duct?

A rectangle has more wall per unit area than a circle, so for the same friction it behaves like a smaller round duct; check the pressure drop with the duct pressure drop calculator.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.